{}

Our Brands

Search FAQs
Where can I find BTU specs for Smart-UPS external battery packs?

Issue:

Where can I find BTU specs for Smart-UPS external battery packs?

Product Line:

Smart-UPS, Smart-UPS Online

Environment:

All external Smart-UPS battery packs, All Serial Numbers

Cause:

Customers look to BTU output specifications when sizing cooling solutions

Resolution:

Because an external battery pack has no charger or other active electronics, it creates no heat unto itself. These products are considered to be an extension of the main UPS unit.  When sizing cooling systems for Smart-UPS products you should use the BTU data provided for the UPS itself, regardless of how many external battery packs are connected.

APC USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: