Search FAQs
Symmetra PX 250/500K power module life cycle alarm
Issue:
Symmetra PX 250/500K power module life cycle alarm
Product line:
Symmetra PX 250/500K
Cause:
Customers may call in to request an FSR or ask how to reset the life cycle alarm on the power modules
Resolution:
The power modules are at end of life and are in need of replacement due to age of wearing components such as fans, capacitors, power supplies, etc. inside of the power module.
There isn’t a reset button to reset the lifecycle. The firmware needs to be upgraded to 4.39 or newer.
FW has been released to change the type of alarm:
Symmetra PX 250-500 Intelligence Module Firmware Upgrade Version 4.39.12.510 (LCM 10yrs EOL) - FSB - 001933
After FW update:
• The display notification becomes INFORMATIONAL (instead of a WARNING)
• No more audible alarm or yellow severity indicator on the display.
• Customers will still be notified that the Power Module has reached the end of its operational life and should be replaced via an Informational notice only.
It is important to note that the modules have reached their end of service life based on a calendar timer. The power module is fully functional and remaining online, the module is not defective or failed. The Advantage Ultra Contract doesn’t cover proactive replacement, so these module DO NOT get replaced under contract.
Keywords:
Symmetra PX 250k, Symmetra PX 500k, Power module life cycle
Symmetra PX 250/500K power module life cycle alarm
Product line:
Symmetra PX 250/500K
Cause:
Customers may call in to request an FSR or ask how to reset the life cycle alarm on the power modules
Resolution:
The power modules are at end of life and are in need of replacement due to age of wearing components such as fans, capacitors, power supplies, etc. inside of the power module.
There isn’t a reset button to reset the lifecycle. The firmware needs to be upgraded to 4.39 or newer.
FW has been released to change the type of alarm:
Symmetra PX 250-500 Intelligence Module Firmware Upgrade Version 4.39.12.510 (LCM 10yrs EOL) - FSB - 001933
After FW update:
• The display notification becomes INFORMATIONAL (instead of a WARNING)
• No more audible alarm or yellow severity indicator on the display.
• Customers will still be notified that the Power Module has reached the end of its operational life and should be replaced via an Informational notice only.
It is important to note that the modules have reached their end of service life based on a calendar timer. The power module is fully functional and remaining online, the module is not defective or failed. The Advantage Ultra Contract doesn’t cover proactive replacement, so these module DO NOT get replaced under contract.
Keywords:
Symmetra PX 250k, Symmetra PX 500k, Power module life cycle
Released for:APC USA
Explore more
Explore more