{}

Our Brands

{"support":{"yesButton":"Yes","noButton":"No","feedback":{"title":"What can we do to improve?"},"submitButton":"Submit","successMessage":"Thank you for your feedback","title":"Was this helpful?","feedbackPercentLabel":"of people found this helpful","captcha":{"error":"Please check the box"}}}

Search FAQs

{"searchBar":{"inputPlaceholder":"Search by keyword or ask a question","searchBtn":"Search","error":"Please enter a keyword to search"}}

Proper use of a "Make Before Break" bypass panel with an SURT or SRT UPS

When moving from Normal to Test mode:

Place UPS into internal Bypass
Confirm UPS is in Bypass
It is now safe to move the SBP to Test mode

When moving from Test to Bypass or vice versa:
UPS can be in any state

When moving from Test back to Normal:

Place UPS into internal Bypass
Confirm that UPS is in Bypass
Move SBP to Normal
Confirm UPS has no faults and input is acceptable to bring online.
Take UPS out of internal Bypass

Can't find what you are looking for?

Reach out to our Customer Care team to receive information on technical support, assistance for complaints and more.