{"support":{"yesButton":"Yes","noButton":"No","feedback":{"title":"What can we do to improve?"},"submitButton":"Submit","successMessage":"Thank you for your feedback","title":"Did this answer your question?","feedbackPercentLabel":"of people found this helpful","captcha":{"error":"Please check the box"}}}
Search FAQs
{"searchBar":{"inputPlaceholder":"Search by keyword or ask a question","searchBtn":"Search","error":"Please enter a keyword to search"}}
Video: How to change the Date on Time on a Network Air FM unit
Issue:
This document will describe how to change the Date on Time on a Network Air FM unit.
Product line:
FM 35-50, IR40, ACFM400, ACFM200.
Environment:
All Serial Numbers.
Cause:
Install, Configuration.
Resolution:
This document will describe how to change the Date on Time on a Network Air FM unit.
Product line:
FM 35-50, IR40, ACFM400, ACFM200.
Environment:
All Serial Numbers.
Cause:
Install, Configuration.
Resolution:
- How to change the Date on Time on a Network Air FM unit.
- Press the ESC Key until you get to the main menu.
- Press ENTER on Setup.
- Press ENTER on System 1.
- Press ENTER on Display.
- Press ENTER on Date/Time.
- Press ENTER on Date to change Date and now you will need to enter a password.
- The default password is 7852 Select each number and then press ENTER to move to the next one.
- Press ENTER on Date again.
- Select Day, Month, and then Year and Press ENTER.
- Press ENTER after changing the Year.
- Press the DOWN arrow and then ENTER to change the TIME.
- Finish by pressing the ENTER key and then press ESC until you get to the status menu.