What are the hole sizes and dimensions of the AR8395 copper bus bar?
Issue:
A customer wants to use 2-hole lugs on the ground bar
Product Line:
NetShelter Bus Bar
Environment:
AR8395
Cause:
Grounding / bonding is required
Resolution:
The AR8395 has the following holes available:
47 holes threaded #10-32, spaced 18 cm center to center.
25 holes at 5.5 cm and 9 holes at 7.9 cm, spaced at 25 cm center to center.
A customer wants to use 2-hole lugs on the ground bar
Product Line:
NetShelter Bus Bar
Environment:
AR8395
Cause:
Grounding / bonding is required
Resolution:
The AR8395 has the following holes available:
47 holes threaded #10-32, spaced 18 cm center to center.
25 holes at 5.5 cm and 9 holes at 7.9 cm, spaced at 25 cm center to center.