{"support":{"yesButton":"Yes","noButton":"No","feedback":{"title":"What can we do to improve?"},"submitButton":"Submit","successMessage":"Thank you for your feedback","title":"Did this answer your question?","feedbackPercentLabel":"of people found this helpful","captcha":{"error":"Please check the box"}}}
Search FAQs
{"searchBar":{"inputPlaceholder":"Search by keyword or ask a question","searchBtn":"Search","error":"Please enter a keyword to search"}}
Video: How to change the set points in an InRow SC system
Issue:
How to change the set points in an ACSC100 unit.
Product line:
ACSC100.
Environment:
All Serial Numbers.
Cause:
Install, Configure.
Resolution:
Press the <ESC> key until you get to the main menu On/Standby
Using the down arrow key scroll until you get to “Set Group Set Points”
Use the <ENTER> key
Enter Password Default=apc
Use the arrows to select character and then use the enter key to go to the next letter. After entering the correct password use enter again.
You can now select any set point and change the value.
How to change the set points in an ACSC100 unit.
Product line:
ACSC100.
Environment:
All Serial Numbers.
Cause:
Install, Configure.
Resolution:
Press the <ESC> key until you get to the main menu On/Standby
Using the down arrow key scroll until you get to “Set Group Set Points”
Use the <ENTER> key
Enter Password Default=apc
Use the arrows to select character and then use the enter key to go to the next letter. After entering the correct password use enter again.
You can now select any set point and change the value.