How humidity threshold alarms are reported on an ACRP
Issue:
This document will describe how humidity threshold alarms are reported on an ACRP.
Product line:
ACRP5XX, ACRP1XX, Uniflair, Network Air FM, ACFM, IR40, InRoom
Environment:
All Product models, all serial numbers
Cause:
Units use dew point to calculate humidity
Resolution:
You may come across an ACRP not generating an alarm message when the Return Humidity is lower than the Threshold [figure 1]. Remember Humidity set points and thresholds are based on dew point. It is possible to be under the RH% set point/threshold and not receive a humidity demand or warning.
This document will describe how humidity threshold alarms are reported on an ACRP.
Product line:
ACRP5XX, ACRP1XX, Uniflair, Network Air FM, ACFM, IR40, InRoom
Environment:
All Product models, all serial numbers
Cause:
Units use dew point to calculate humidity
Resolution:
You may come across an ACRP not generating an alarm message when the Return Humidity is lower than the Threshold [figure 1]. Remember Humidity set points and thresholds are based on dew point. It is possible to be under the RH% set point/threshold and not receive a humidity demand or warning.
Figure 1