APC Schneider Cooling Unit Identification
2= 208-230/1/60 3= 277/ 1 / 60 A = Air Cooled
Smart-UPS VT-g3500; installation, recommended breaker and cable sizes
Single Mains ... 10kva 35 A fast acting class J fuse 15kva 60 A fast acting class J fuse 20kva 80 A fast acting class J fuse 30kva 125 A fast acting class J fuse ... 10kva 8 8 1 15kva 6 6 1 20kva 4 4 1 30kva 1 1 1 ... 1 YA1CL2TC38 MD7-34R W1CVT 0.2in/6mm
Technical Spec’s on a acpa4000
... Supply 115/ 60 / 1 Power Consumption ( ... /hr is a measure of energy Current Consumption ( A ) 14.4 A Fuse Size ( A ) 20a Plug CFG NEMA 5 - 20 Min-Max Voltage 110-120
Does the 600mm units have any contact output/inputs?
Yes, it has a form C alarm relay. It also has a single voltage level input (24V AC/DC nominal).
Why can't I use a domestic model APC UPS on a ship
ground, one will see 60 volts . Product Line:
How do I reset the password on my IP or Analog KVM (ap5401 or ap5405 only) or Console Port Server (ap9301/ap9302/ap9303)?
... , immediately type a <space> as many times ... need to for it to register a single space, then type the word single
What is the input voltage required for the InRow acrd100/200? Is a power cord supplied with the unit?
The InRow RD unit uses a single phase 208v/60hz input in NAM and a 230v/50hz input in the rest of the ...
What is the input voltage required for the InRow ACRD?
The InRow ACRD unit uses a single phase 208v/60hz input in NAM and a 230v/50hz input in the rest of the ...
Information on Online and On Battery operation of 3:1 Symmetra UPS systems
... of 3: 1 Symmetra UPS systems ... 3: 1 (International) ... ... of 3: 1 Symmetra UPS systems When a Symmetra 3: 1 is operating On ... ... per phase with a maximum 16KVA load ... ... and converted to single phase and sent ... ... The nominal input voltage range is 380 or 400 or 415. ... .7 = 400 ; 240 x ... ... Symmetra 3: 1 will run On ... The output voltage can be set ... at 50 or 60 Hertz. If any one of the phases ... ... no more than 60 amps per phase ... If phase A or B fails ...
Humidity Sensor Issue with 300/303/310/400 Series Appliances
... require humidity thresholds above 60 % or if ... toll free at 1 -877- ... you to determine a solution that meets your requirements.