APC Smart-UPS 2200 120V
SU2200
Discontinued on:10 June 2022
Recommended replacement(s)
SU2200 is replaced by:
+ Lifecycle Services
Specifications
Lead time | Usually in Stock |
---|
Run time for load WEnter the total load (power draw) of all devices that will be protected by the UPS. This will be used to estimate the run time of your devices during a total power outage. Adding run time increases availability by allowing the system to operate through longer outages without shutting down. Min-max: 160-1600 W | |
---|---|
Max. Capacity Used The maximum percentage of UPS capacity used to support your specified load. | |
Main Input Voltage | 120 V |
Main Output Voltage | 120 V |
Kw Rating | 1600 W |
rated power in VA | 2200 VA |
plug standard | NEMA 5-20P |
nb of power socket outlets | 8 NEMA 5-15R |
number of rack unit | 0U |
cable length | 6 ft (1.83 m) |
number of cables | 1 |
Battery Type | Lead-Acid battery |
provided equipment | User Manual Smart UPS signalling RS-232 cable CD with software |
Number of power module filled slots | 0 |
---|---|
Number of power module free slots | 0 |
redundant | No |
color | Beige |
---|---|
Height | 17.01 in (43.2 cm) |
Width | 7.72 in (19.6 cm) |
Depth | 21.50 in (54.6 cm) |
Net Weight | 112.24 lb(US) (50.91 kg) |
Mounting Location | Front |
mounting preference | No preference |
Mounting Mode | Not rack-mountable |
USB compatible | No |
Efficiency at full load | 86...154 V adjustable 92...147 V |
---|---|
Input Frequency | 50/60 Hz +/- 3 Hz auto-sensing |
crest factor | Up to 5 : 1 |
---|---|
harmonic distortion | Less than 5 % at full load |
Maximum configurable power in VA | 2200 VA |
Max Configurable Power (Watts) | 1600 W |
Transfer Time | 2ms typical |
Topology | Line Interactive |
Waveform Type | Sine wave |
Output Frequency (sync to mains) | 47...53 Hz for 50 Hz nominal sync to mains 57...63 Hz for 60 Hz nominal sync to mains |
Product Certifications | CSA |
---|---|
Equipment protection policy | Lifetime : $150000 |
standards | FCC Part 15 class A UL 1778 |
acoustic level | 45 dBA |
---|---|
heat dissipation | 275 Btu/h |
operating altitude | 0...10000 ft |
Ambient Air Temperature for Operation | 32…104 °F (0…40 °C) |
Ambient Air Temperature for Storage | 5…113 °F (-15…45 °C) |
storage altitude | 0…50000 ft (0.00…15240.00 m) |
Relative Humidity | 0…95 % |
Storage Relative Humidity | 0…95 % |
Run Time | View Runtime Graph |
---|---|
Extendable Run Time | 0 |
Included Battery Modules | 0 |
Battery Slots Empty | 0 |
Typical recharge time | 3 h |
RBC Quantity | 1 |
Battery Life | 3…5 year(s) |
Battery power in VAH | 816 VAh runtime |
Battery Charge Power (Watts) | 271 W rated |
Audible Alarm | Alarm when on battery : distinctive low battery alarm : configurable delays |
---|---|
Control panel | LED status display with load and battery bar-graphs and On Line : On Battery : Replace Battery : and Overload Indicators |
Emergency Power Off (EPO) | Optional |
free slots | 1 |
Surge energy rating | 320 J |
---|---|
Filtering | Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : m |
GTIN | 731304011040 |
---|---|
Package weight(Lbs) | 134.28 lb(US) (60.91 kg) |
Warranty | 2 years repair or replace, optional on-site warranties available, optional extended warranties available |
---|
Documents
Software and Firmware
Items usually bought together
Need more information? Check our technical FAQs!
Easily find answers to the most frequently asked questions.