1 videos
Galaxy VS UPS 150kW 400V for External Batteries, Start-up 5x8
GVSUPS150KHS
Environmental performance of the product Learn more
Sustainable by Design
Specifications
Presentation | Highly efficient, easy-to-deploy 150kW, 400V 3-phase UPS that brings best-in-class power protection and low total cost of ownership to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. Includes 5x8 start-up service. See the battery runtime chart for details. |
---|---|
Lead time | Usually Ships within 2 Weeks |
Main Input Voltage | 400 V 3 phase |
---|---|
Other Input Voltage | 380 V 415 V |
Main Output Voltage | 400 V 3 phase |
Other Output Voltage | 380 V 415 V |
Kw Rating | 150 kW |
Rated power in VA | 150 kVA |
Battery Type | External battery system Li-Ion (Lithium Ion) VRLA |
provided equipment | Dust filter EcoStruxure IT ready (UPS) Installation guide Integrated network management Power modules ship installed Start-Up Service |
Bypass Voltage Tolerance | +/- 10 % |
---|---|
Redundant | No |
color | White |
---|---|
Height | 58.46 in (148.5 cm) |
Width | 20.51 in (52.1 cm) |
Depth | 33.35 in (84.7 cm) |
Net Weight | 639.34 lb(US) (290 kg) |
USB compatible | No |
Input Frequency | 40 - 70 Hz |
---|---|
Efficiency at full load | 340...460 V 400 V |
Maximum Input Current per Phase | 270 A |
Maximum Short Circuit Withstand (Icw) | 65 kA |
Input Total Harmonic Distortion | Less than 3% for full load |
Load power factor | From 0.7 leading to 0.7 lagging without any derating |
Input Power Factor at Full Load | 0.99 |
Max Configurable Power (Watts) | 150 kW |
---|---|
output frequency | 50 Hz sync to mains 60 Hz sync to mains 50 Hz +/- 0.1 % for 50 Hz nominal not synced 60 Hz +/- 0.1 % for 60 Hz nominal not synced |
Crest factor | 2.5 |
Waveform Type | Sine wave |
Output voltage tolerance | +/-1% after 50ms |
Overload Operation | 10 minutes @ 125% and 60 seconds @ 150% |
Bypass type | Built-in Static Bypass |
Maximum configurable power in VA | 150 kVA |
Standards | IEC 62040-1-1 IEC 62040-2 IEC 60721-4-2 Level 2M2 OSHPD UL 1778 5th edition |
---|
Ambient Air Temperature for Operation | 32…104 °F (0…40 °C) |
---|---|
Relative Humidity | 0…95 % non-condensing |
Operating altitude | 0...3333 ft |
Ambient Air Temperature for Storage | -13…131 °F (-25…55 °C) |
Storage Relative Humidity | 10…80 % non-condensing |
Acoustic level | 65 dBA |
Heat dissipation | 16900 Btu/h |
IP degree of protection | IP21 |
Efficiency | View Efficiency Graph |
---|---|
Battery Voltage | 480-576VDC |
End of Discharge Battery Voltage | 384 V DC |
End of Discharge Maximum Battery Current | 407 A |
Battery power in VAH | 0 VAh runtime |
Extendable Run Time | 0 |
Free slots | 1 |
---|---|
control panel | Touch Screen LCD User Interface |
Audible Alarm | Audible and visible alarms prioritized by severity |
GTIN | 731304407911 |
---|
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 66.14 in (168 cm) |
Package 1 Width | 38.98 in (99 cm) |
Package 1 Length | 25.20 in (64 cm) |
Package 1 Weight | 694.46 lb(US) (315 kg) |
Warranty | 1 year on-site repair or replace with factory authorized Start-Up |
---|
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-class environmental performance.
Green Premium promises compliance with the latest regulations, transparency on environmental impacts, as well as circular and low-CO2 products.
Learn more
Resource performance
Energy efficient product
Take-back program available
Well-being performance
Mercury free
Certifications & Standards
REACh Regulation
EU RoHS Directive
China RoHS Regulation
Environmental Disclosure
Circularity Profile
Documents
Software and Firmware
Need more information? Check our technical FAQs!