Oil Type for Different Types of Refrigerant
Issue:
Oil Type for Different Types of Refrigerant
Product line:
All AC DX Units
Environment:
All versions/serials
Cause:
Oil Maintenance
Resolution:
Below is a list of the different oil types for the different refrigerants in our units. Always check the compressor manufacture's recommendations for oil on any other type of cooling unit.
R 12 Use Mineral Oil or Alkyl Benzene Oil
R 22 Use Mineral Oil, Mixing of POE is acceptable however it is preferred to use the oil that the original charge used. Units: AX, CM, CC T, DT, TC, FM, ACPA4000, AP7003
R134A Use POE oil Units: RDU but no oil needed for this unit on startup.
R407C Use POE oil Units: ACRP, ACRD5xx, Stulz
R410A Use PVE oil Units: ACRD1XX, ACRD2XX, ACRD3XX,ACRD60XX, ACRD6XXP ACSC, Uniflair, ACPSC, Ecobreeze
POE oil recommendations 150, 160 Viscosity.
Copelands POE oil Part# 998-E022-01
Ultra 32-3MAF
PVE oil recommendations 320HV or FVC68D or better yet Danfos 120Z5034
Schneider-Electric Sku for POE oil: 0J-9099
Note: Prior to adding any oil to a system a leak check should be completed and a proper acid test completed.
Oil Type for Different Types of Refrigerant
Product line:
All AC DX Units
Environment:
All versions/serials
Cause:
Oil Maintenance
Resolution:
Below is a list of the different oil types for the different refrigerants in our units. Always check the compressor manufacture's recommendations for oil on any other type of cooling unit.
R 12 Use Mineral Oil or Alkyl Benzene Oil
R 22 Use Mineral Oil, Mixing of POE is acceptable however it is preferred to use the oil that the original charge used. Units: AX, CM, CC T, DT, TC, FM, ACPA4000, AP7003
R134A Use POE oil Units: RDU but no oil needed for this unit on startup.
R407C Use POE oil Units: ACRP, ACRD5xx, Stulz
R410A Use PVE oil Units: ACRD1XX, ACRD2XX, ACRD3XX,ACRD60XX, ACRD6XXP ACSC, Uniflair, ACPSC, Ecobreeze
POE oil recommendations 150, 160 Viscosity.
Copelands POE oil Part# 998-E022-01
Ultra 32-3MAF
PVE oil recommendations 320HV or FVC68D or better yet Danfos 120Z5034
Schneider-Electric Sku for POE oil: 0J-9099
Note: Prior to adding any oil to a system a leak check should be completed and a proper acid test completed.