    Is COO, HTTS or ECCN information available for NetShelter CX cabinets and accessories?
    ar4701 Dust Filter Pack NetShelter CX 18U & 24U 2 Small Filters
    What is the Thermal Capacity of the NetShelter CX Mini and CX2?
    Define the thermal capacity of the NetShelter CX . ... NetShelter CX ... ar4000mv NetShelter CX Mini = 800w ar4018a / ar4018ia NetShelter CX 18U = 1.2kw ar4024a / ar4024ia NetShelter CX 24U = 2 .4kw ar4038a / ar4038ia NetShelter CX 38U = 3.6kw.
    What is the IP (Internal Protection) rating of the NetShelter SX, SV and CX cabinets?
    ... rating of the NetShelter SX, SV and CX cabinets is required ... NetShelter SX, NetShelter SV, NetShelter CX The NetShelter cabinets have not ... The NetShelter SX and SV ... This includes : ar3100, ... The NetShelter CX meet the Internal ... This includes : ar4000mv, ... ... With the optional dust filters installed they meet ... 2 = Protects against ... 5 = Dust protected 6 = Dust tight 2 = Protects against ... The NetShelter SX and SV ... The NetShelter CX cabinet meets the ... Plus, if the optional dust filters are used the CX will protect against dust and splashing water, which meets the rating scale of IP54.
    In the NetShelter CX Enclosure Brochure the number of outlets per cabinet does not match the number of ports on the PDU, why?
    The 18U cabinet has one fan module, the 24U has two fan modules, the 38U has three fan modules.
    What is the power consumption of the fans in the NetShelter CX?
    A customer needs to know how much power is consumed by the NetShelter CX fans. ... NetShelter CX ... NetShelter CX Mini = 30w NetShelter CX /CX2 18U = 34W NetShelter CX /CX2 24U = 68W NetShelter CX /CX2 38U = 101w
    What is the cfm rating of the NetShelter CX with ar4703 installed?
    Customers want to know the cfm rating of NetShelter CX cabinets with the ar4703 fan booster installed. ... NetShelter CX . ... Installing the ar4703 increases the cfm of the NetShelter CX cabinet. ... 18U with 1x ar4703 - 260 CFM 24U with 2 x ar4703 - 330 CFM
    Is the PDU removable that's included inside the NetShelter CX ar4000mv?
    Issue: A customer wants to replace the PDU in a NetShelter CX Mini .
    What should be checked if the NetShelter CX internal temperature exceeds expected levels? (5*C/41*F above room temp)
    Excessive temperature in NetShelter CX . ... NetShelter CX ... Fan issues, air recirculation, cabinet overloaded, intake/exhaust blocked, filter , wall clearance. ... 2 . Check that the foam clamp is fastened tightly around the cables exiting the cabinet otherwise air will be drawn through the gap and straight into the air inlets of the fan modules, thus bypassing the internal equipment.
    Results 1 - 10 of 50