Single Phase Symmetra SmartSlot Device Installation
Published date:
15 October 2013
Issue:
In order to ensure proper operation, SmartSlot cards must be installed in a certain, specific order according to precedence
Product Line:
Single Phase Symmetra and smart-slot accessories.
Note: Only SmartSlot accessories with revision K or later can be integrated with the Symmetra.
Resolution:
When placing multiple SmartSlot accessories in the Symmetra expansion slots, great care must be taken so the correct ordering of the accessories observed. A SmartSlot device with higher priority must be placed in the SmartSlot labeled with the higher number. Refer to the following table for details.
Second-highest-numbered slot (highest if no network management card is present)
Dry Contact I/O SmartSlot Card
AP9610
AP9613
Medium
Any slot numbered lower than a network management card, Call-UPS II; any slot higher than Measure-UPS
Interface Expander SmartSlot Card
AP9607
Medium
Any slot numbered lower than a network management card, Call-UPS II; any slot higher than Measure-UPS
Measure-UPS SmartSlot Card
AP9612T
AP9612TH
Lowest
Lowest-numbered slot
The following graphic is an example of how to install multiple SmartSlot devices in the Symmetra Power Array. Please note the numbering shown in the figure. The network management card is installed in slot #4, Call-UPS II in #3, Interface Expander in #2, and Measure- UPS in #1.
The following graphic is an example of how to install multiple SmartSlot devices in the Symmetra RM and Symmetra LX. The network management card is installed in slot #2 and Call-UPS II is installed in slot #1.