Symmetra PX 10kW Power Module, 208V

Symmetra PX 10kW Power Module, 208V Front Left
Symmetra PX 10kW Power Module, 208V Front Left
Symmetra PX 10kW Power Module, 208V Front Left
Symmetra PX 10kW Power Module, 208V Back
Symmetra PX 10kW Power Module, 208V Front Left
Symmetra PX 10kW Power Module, 208V Back
  • High density, double-conversion on-line power protection with scalable runtime

  • Includes: Installation guide

View Product Overview
Replacement battery
User replaceable battery not available

SYPM10KF Features

Key Features

Run time for load
Min-max
W
Run time for load
Enter the total load (power draw) of all devices to be protected by the UPS here. Based on the value entered we will estimate the run time that you will have during a total power outage. Adding run time increases availability by allowing the system to operate through longer outages without shutting down.

The total load (power draw) entered exceeds the maximum value for this product (10000 W)

Please enter load to see estimated run time

The total load (power draw) entered is less than the minimum value for this product ({} W)

Max. Capacity Used
Max. Capacity Used
The maximum percentage of UPS capacity used to support your specified load.

Please enter load to see calculated "Max. Capacity Used"

Output power capacity
10.0kWatts / 10.0kVA
Rack Height
3U
Output Connections
(1) Hard wire 5-wire (3P + N + E) (Battery Backup)
Nominal Output Voltage
208V, 208V 3PH
Nominal Input Voltage
208V, 208V 3PH
Input Connections
Hard wire 5-wire (3P + N + E)
Symmetra PX 10kW Power Module, 208V
High density, double-conversion on-line power protection with scalable runtime
Includes: Installation guide

Product Distribution

Antigua and Barbuda, Anguilla, Netherlands Antilles, Argentina, Aruba, Barbados, Bermuda, Bolivia, Brazil, Bahamas, Belize, Canada, Chile, Colombia, Costa Rica, Dominica, Dominican Republic, Ecuador, Grenada, Guadeloupe, Guatemala, Guyana, Honduras, Haiti, Jamaica, Saint Kitts And Nevis, Cayman Islands, Saint Lucia, Martinique, Mexico, Nicaragua, Panama, Peru, Puerto Rico, Paraguay, El Salvador, Turks And Caicos Islands, Trinidad and Tobago, United States, Uruguay, Saint Vincent And The Grenadines, Venezuela, U.S. Virgin Islands

Technical Specifications

Output

Max Configurable Power (Watts)
10.0kWatts / 10.0kVA
Efficiency at Full Load
92.0 %
Output Voltage Distortion
Less than 5 % at full load
Output Frequency (sync to mains)
57 - 63 Hz For 60 Hz nominal Sync to mains, 60 Hz +/- 0.1 % For 60 Hz nominal Unsynchronised
Load Crest Factor
Unlimited
Topology
Double conversion online
Waveform type
Sine wave

Input

Input frequency
60 Hz +/- 3 Hz
Input voltage range for main operations
177 - 239 (208 V)V
Number of Power Cords
1
Efficiency at Full Load
92.0 %
Input Power Factor at Full Load
0.99

Communications & Management

Audible Alarm
Alarm when on battery : distinctive low battery alarm : configurable delays

Physical

Maximum Height
5.24inches (133MM, 13.3CM)
Maximum Width
19.02inches (483MM, 48.3CM)
Maximum Depth
27.56inches (700MM, 70.0CM)
Net Weight
58.11lbs. (26.36KG)
Shipping weight
70.15lbs. (31.82KG)
Shipping Height
10.75inches (273MM, 27.3CM)
Shipping Width
22.01inches (559MM, 55.9CM)
Shipping Depth
32.76inches (832MM, 83.2CM)
Color
Black
Units per Pallet
8.0

Environmental

Operating Temperature
32 - 104 °F (0 - 40 °C)
Operating Relative Humidity
0 - 95 %
Operating Elevation
0 - 3333ft (0 - 1015.9meters)
Storage Temperature
-40 - 70 °C
Audible noise at 1 meter from surface of unit
64.0dBA
Online thermal dissipation
2970.0BTU/hr

Conformance

Approvals
CUL listed, FCC part 15 class A, ISO 14001, ISO 9001, UL 60950, UL listed
Standard warranty
1 year repair or replace

Options