InRow RC, 600mm, Chilled Water, 200-240V, 50/60Hz

InRow RC, 600mm, Chilled Water, 200-240V, 50/60Hz Front Left
InRow RC, 600mm, Chilled Water, 200-240V, 50/60Hz Front Left
InRow RC, 600mm, Chilled Water, 200-240V, 50/60Hz Front Left
InRow RC, 600mm, Chilled Water, 200-240V, 50/60Hz Front Left
InRow RC, 600mm, Chilled Water, 200-240V, 50/60Hz Detailed
  • Close-coupled, chilled water cooling for medium to large data centers

  • Includes: Installation guide, Operations and maintenance manual

View Product Overview

ACRC500 Features

InRow RC, 600mm, Chilled Water, 200-240V, 50/60Hz
Close-coupled, chilled water cooling for medium to large data centers
Includes: Installation guide, Operations and maintenance manual

InRow Chilled Water Cooling Features & Benefits

Total Cost of Ownership

Row-based architecture
Captures hot exhaust air directly from the IT equipment, thereby increasing the unit's sensible cooling capacity over traditional cooling architectures.
Variable speed fans
Variable speed fans reduce energy consumption during off-peak cooling periods.

Agility

Casters
Provides flexibility to move the unit to wherever cooling is required.
Scaleable densities
Allows for higher densities to be achieved by integrating containment with room, row and rack cooling system architectures.
Modular design
Modular design provides scalable solutions to add cooling as demand increases.

Serviceability

Easy service access
Allows for all serviceable components to be replaced/maintained by easily accessible panels/doors.

Manageability

Building management system integration
Send alarms and data points allowing you to manage critical building infrastructure from a single system.
Microprocessor controller
Provides proactive control and real-time monitoring via a four line, eighty character, alphanumeric display.
Real-Time Capacity Monitoring
Real-time display of current and available cooling.

Availability

Dual A-B power inputs
Draws power from the UPS for power protection with dual feeds for redundancy.
Rack inlet control
Rack inlet control guarantees inlet temperature to IT equipment.
Top and bottom chilled water connections
Allows chilled water to be connected from the top, if routing from overhead, or bottom, if on a raised floor.
Active response controls
Monitors and actively adjusts cooling capacity to ensure proper server inlet temperatures. Through the microprocessor controller, visibility into the operation and health of the unit is provided.
Predictable cooling
Placing the unit in the row of racks moves the source of cooling closer to the heat load. This eliminates air mixing and provides a predictable cooling architecture.

Product Distribution

Antigua and Barbuda, Anguilla, Netherlands Antilles, Aruba, Barbados, Bermuda, Bolivia, Belize, Canada, Colombia, Costa Rica, Cuba, Dominican Republic, Ecuador, Falkland Islands, Guatemala, Guyana, Honduras, Jamaica, Mexico, Nicaragua, Panama, Peru, Philippines, Puerto Rico, El Salvador, Trinidad and Tobago, United States, Venezuela, U.S. Virgin Islands

Input

Nominal Input Voltage
200V 3PH, 208V 3PH
Input frequency
50/60 Hz
Input Connections
NEMA L21-20P
Number of Power Cords
2

Communications & Management

Control panel
Multi-function LCD status and control console
Audible Alarm
Audible and visible alarms prioritized by severity

Physical

Maximum Height
78.39inches (1991MM, 199.1CM)
Maximum Width
23.62inches (600MM, 60.0CM)
Maximum Depth
42.13inches (1070MM, 107.0CM)
Rack Height
42U
Net Weight
760.0lbs. (345.45KG)
Shipping weight
892.0lbs. (405.45KG)
Shipping Height
85.29inches (2166MM, 216.6CM)
Shipping Width
33.47inches (850MM, 85.0CM)
Shipping Depth
44.75inches (1137MM, 113.7CM)
Color
Black
Units per Pallet
1.0

Conformance

Approvals
cUL Listed, CE, Industry Canada, UL Listed, VDE
Standard warranty
1 year (parts only), 1 year on-site repair or replace with factory authorized Start-Up

General

Air Discharge Patterns
Horizontal
Air Flow
6000.0CFM (2831.68lps)
Condensate Pump Capacity
8.45gal/hour (0.008lps)
Intake Air
Rear Return
Minimum Water Inlet Temperature
45.0 °F (7.0 °C)