MGE Galaxy 7000 250 kVA

MGE Galaxy 7000 250 kVA Front Left
MGE Galaxy 7000 250 kVA Front Left
MGE Galaxy 7000 250 kVA Front Left
MGE Galaxy 7000 250 kVA Front Left
MGE Galaxy 7000 250 kVA Miscellaneous
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getAggregateRating, 106ms
  • REVIEWS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 53ms
  • REVIEWS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
  • A high-adaptability, 3-phase UPS that meets the unique requirements of medium to large data centers, industry, buildings, and mission-critical environments. This ...

  • Includes: Installation guide, Network Management Card, User Manual

View Product Overview

G7TUPS250 Features

MGE Galaxy 7000 250 kVA
A high-adaptability, 3-phase UPS that meets the unique requirements of medium to large data centers, industry, buildings, and mission-critical environments. This UPS includes ECO Mode, with cost-saving energy efficiency, and SPoT operation mode, which increases on-site test capability without additional load bank.
Includes: Installation guide, Network Management Card, User Manual
  • Audible alarms
    Provides notification of changing utility power and UPS power conditions
  • Generator compatible
    Ensures clean, uninterrupted power to protected equipment when generator power is used.
  • Manual maintenance bypass
    Reduces installation costs by eliminating the need for an external mechanical bypass.

Galaxy 7000 Features & Benefits

Sustainability

EU CoC for UPS
Ensures that UPSs sold in the EU are highly efficient

Economy

Fully-rated power kVA equals kW
Reduces cost by eliminating the need for an oversized UPS for Power Factor Corrected (PFC) loads.
ECO Mode
Operating mode that by-passes unused electrical components in good power conditions to achieve high operating efficiency without sacrificing protection
Advanced electrical features
Excellent power conditioning, very low harmonic distortion through IGBT rectifier, input power factor correction, and high power efficiency

Manageability

Network management capability
Full-featured network management interfaces that provide standards-based management via Web, SNMP, and Telnet.

Availability

High availability architecture
Different running modes : hot stand-by, integrated parallel, or centralized static switch for multi-modules leading to availability architectures

Compatibility

Compatible with Schneider Electric's lithium ion battery solution
Reduces system footprint and weight, cooling and maintenance requirements, and total cost of ownership; offers double the life of VRLA batteries; and improves backup storage predictability and manageability.
Click here for more details.
Output synchronization to external source
UPS systems can be synchronized with any other independent source for use with downstream static transfer switches.
Parallel capability
Multiple units can be placed in parallel to meet power capacity and redundancy requirements

Product Distribution

Andorra, United Arab Emirates, Afghanistan, Antigua and Barbuda, Anguilla, Albania, Armenia, Netherlands Antilles, Angola, Argentina, Austria, Australia, Aruba, Azerbaijan, Bosnia and Herzegovina, Barbados, Bangladesh, Belgium, Burkina Faso, Bulgaria, Bahrain, Burundi, Benin, Bermuda, Brunei, Bolivia, Brazil, Bahamas, Bhutan, Botswana, Belarus, Belize, The Democratic Republic Of Congo, Central African Republic, Congo, Switzerland, Côte d'Ivoire, Cook Islands, Chile, Cameroon, China, Colombia, Costa Rica, Serbia and Montenegro, Cuba, Cyprus, Czech Republic, Germany, Djibouti, Denmark, Dominica, Dominican Republic, Algeria, Ecuador, Estonia, Egypt, Western Sahara, Eritrea, Spain, Ethiopia, Finland, Fiji, Falkland Islands, France, Gabon, United Kingdom, Grenada, Georgia, French Guiana, Ghana, Gibraltar, Gambia, Guinea, Guadeloupe, Equatorial Guinea, Greece, Guatemala, Guyana, Hong Kong, Honduras, Croatia, Haiti, Hungary, Indonesia, Ireland, Israel, India, Iraq, Iran, Iceland, Italy, Jamaica, Jordan, Kenya, Cambodia, Saint Kitts And Nevis, South Korea, Kuwait, Cayman Islands, Kazakhstan, Lebanon, Saint Lucia, Liechtenstein, Sri Lanka, Liberia, Lesotho, Lithuania, Luxembourg, Latvia, Morocco, Moldova, Madagascar, Macedonia, Mali, Myanmar, Mongolia, Martinique, Mauritania, Malta, Mauritius, Malawi, Malaysia, Mozambique, Namibia, Niger, Nigeria, Nicaragua, Netherlands, Norway, Nepal, New Zealand, Oman, Panama, Peru, Papua New Guinea, Philippines, Pakistan, Poland, Puerto Rico, Portugal, Paraguay, Reunion, Romania, Russia, Rwanda, Saudi Arabia, Sudan, Sweden, Singapore, Slovenia, Slovakia, Sierra Leone, Senegal, Somalia, Suriname, El Salvador, Turks And Caicos Islands, Chad, Togo, Thailand, Tajikistan, Turkmenistan, Tunisia, TP, Turkey, Trinidad and Tobago, Taiwan, Tanzania, Ukraine, Uganda, Uruguay, Uzbekistan, Saint Vincent And The Grenadines, Venezuela, U.S. Virgin Islands, Vietnam, XF, Yemen, Mayotte, South Africa, Zambia, Zimbabwe

Output

Output power capacity
225.0kWatts / 250.0kVA
Max Configurable Power (Watts)
225.0kWatts / 250.0kVA
Nominal Output Voltage
400V 3PH
Neutral Output Current
541A
Output Voltage Note
Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
Output Voltage Distortion
Less than 2%
Output Frequency (sync to mains)
50 Hz, 60 Hz
Output Frequency (not synced)
60Hz +/- 0.1% for 60Hz nominal, 50Hz +/- 0.1% for 50Hz nominal
Other Output Voltages
380, 415, 440
Load Crest Factor
3 : 1
Topology
Double Conversion Online
Waveform type
Sine wave
Maximum Output Current
1281
Output Voltage THD
< 2% linear load and <3% non-linear load
Bypass
Built-in Maintenance Bypass

Input

Nominal Input Voltage
400V 3PH
Input frequency
45 - 65 Hz
Input Connections
Hard Wire 5-wire (3PH + N + G)
Input voltage range for main operations
340 - 460 (400V)V
Input Total Harmonic Distortion
Less than 3% for full load
Type of Input Protection Required
3-pole breaker
Other Input Voltages
380, 415, 450
Maximum Short Circuit Withstand (Icw)
200.0kAmps
Maximum Input Current
365.0A
Input Power Factor at Full Load
1.0

Batteries & Runtime

Battery type
VRLA

Communications & Management

Pre-Installed SmartSlot™ Cards
Control panel
Multi-function LCD status and control console
Audible Alarm
Audible and visible alarms prioritized by severity
Emergency Power Off (EPO)
Yes
Available SmartSlot™ Interface Quantity
1

Physical

Maximum Height
1900MM, 190.0CM
Maximum Width
1412MM, 141.2CM
Maximum Depth
855MM, 85.5CM
Net Weight
960.0KG
Shipping weight
980.0KG
Shipping Height
2030MM, 203.0CM
Shipping Width
1520MM, 152.0CM
Shipping Depth
960MM, 96.0CM
Color
Grey
# of Layers per Pallet
1.0
# of Units per Layer per Pallet
1.0

Environmental

Operating Temperature
0 - 35 °C
Operating Relative Humidity
20 - 80 %
Operating Elevation
0-999.9meters
Storage Temperature
-25 - 40 °C
Storage Relative Humidity
20 - 80 %
Storage Elevation
0-9000meters
Audible noise at 1 meter from surface of unit
70.0dBA
Protection Class
IP 20

Conformance

Approvals
CE, EN 60950, EN/IEC 62040-2, EN/IEC 62040-3, ISO 14001, ISO 9001, LCIE, VFI-SS-111
Standard warranty
1 year repair or replace

Sustainable Offer Status

Battery Directive
Compliant

General

Bypass Connection
4 wire (3Ph + N) or 5 wire (3Ph + N + G)
Bypass Protection Device
630.0
Max Bypass Input Current
422.0A

Options

Services