InRow DX 300mm 30kW

InRow DX 300mm 30kW Front Left
InRow DX 300mm 30kW Front Left
InRow DX 300mm 30kW Front Left
InRow DX 300mm 30kW Front Straight
InRow DX 300mm 30kW Back
InRow DX 300mm 30kW Application
InRow DX 300mm 30kW Application
InRow DX 300mm 30kW Front Left
InRow DX 300mm 30kW Front Straight
InRow DX 300mm 30kW Back
InRow DX 300mm 30kW Application
InRow DX 300mm 30kW Application
  • Close-coupled, air, water, and glycol cooling for closets, server rooms, and data centers

  • Includes: Installation guide, Integrated network management, Network management card, Optional concrete pad, User manual

View Product Overview

ACRD301S Features

Key Features

Rack Height
42U
InRow DX 300mm 30kW
Close-coupled, air, water, and glycol cooling for closets, server rooms, and data centers
Includes: Installation guide, Integrated network management, Network management card, Optional concrete pad, User manual

Uniflair Direct Expansion InRow Cooling Features & Benefits

Availability

Active response controls
Monitors and actively adjusts cooling capacity to ensure proper server inlet temperatures. Through the microprocessor controller, visibility into the operation and health of the unit is provided.
Predictable cooling
Placing the unit in the row of racks moves the source of cooling closer to the heat load. This eliminates air mixing and provides a predictable cooling architecture.
Rack inlet temperature control
Reduces the risk of hot spots at the rack level

Manageability

Microprocessor controller
Utilizes intelligent, active response control, and real-time monitoring. The system is controlled by a microprocessor providing high level control functionality and human interface via a four line, eighty character, alphanumeric display
Real-Time capacity monitoring
Real-time display of current and available cooling.
Building management system integration
Send alarms and data points allowing you to manage critical building infrastructure from a single system.

Serviceability

Easy service access
Allows for all serviceable components to be replaced/maintained by easily accessible panels/doors.

Total cost of Ownership

Row-based architecture
Captures hot exhaust air directly from the IT equipment, thereby increasing the unit's sensible cooling capacity over traditional cooling architectures.
Variable speed fans
Variable speed fans reduce energy consumption during off-peak cooling periods.

Agility

Modular design
Modular design provides scalable solutions to add cooling as demand increases.
Scalable densities
Allows for higher densities to be achieved by integrating containment with room, row and rack cooling system architectures.

Product Distribution

United Arab Emirates, Argentina, Austria, Australia, Belgium, Bulgaria, Brazil, Canada, Switzerland, Chile, China, Colombia, Costa Rica, Serbia and Montenegro, Czech Republic, Germany, Denmark, Algeria, Estonia, Egypt, Spain, Finland, France, United Kingdom, Greece, Hong Kong, Croatia, Hungary, Indonesia, Ireland, Israel, India, Italy, Japan, South Korea, Kazakhstan, Lithuania, Latvia, Morocco, Macedonia, Mexico, Malaysia, Nigeria, Netherlands, Norway, New Zealand, Peru, Philippines, Poland, Portugal, Romania, Russia, Saudi Arabia, Sweden, Singapore, Slovenia, Slovakia, Thailand, Tunisia, Turkey, Taiwan, Ukraine, United States, Vietnam, South Africa

Technical Specifications

Input

Input frequency
50/60 Hz
Power Feeds
2.0
Input Power
850 Watts
Maximum Overcurrent Protection
25.0A
Minimum Circuit Amp Capacity
20.0

Communications & Management

Control panel
Multifunction LCD status and control console
Audible Alarm
Audible and visible alarms prioritized by severity

Physical

Maximum Height
1991MM, 199.1CM
Maximum Width
300MM, 30.0CM
Maximum Depth
1095MM, 109.5CM
Net Weight
159.98KG
Shipping weight
200.0KG
Shipping Height
2152MM, 215.2CM
Shipping Width
661MM, 66.1CM
Shipping Depth
1137MM, 113.7CM

Environmental

Operating Temperature
-25 - 46 °C
Operating Relative Humidity
0 - 95 %
Operating Elevation
0 - 3048meters
Storage Temperature
-20 - 46 °C
Audible noise at 1 meter from surface of unit
77.1dBA

Conformance

Approvals
CE, CUL listed, UL listed
Standard warranty
1 year on-site repair or replace with factory authorized Start-Up

General

Air Discharge Patterns
Horizontal
Air Flow
1604.62lps
Compressor Type
Scroll
Intake Air
Rear return
Refrigerant Charge
14.97pounds

Options

Services