Symmetra PX 128kW Scalable to 160kW, without Bypass, Distribution, or Batteries, 400V

Share:

Symmetra PX 128kW Scalable to 160kW, without Bypass, Distribution, or Batteries, 400V

SY128K160H-NB

Description: A high-efficiency, modular 3-phase UPS that offers internal redundancy for your data center requirements. With scalable power, this UPS grows with your data center up to 160kW/kVA. Pair with the Classic Battery Cabinet and the Wall-Mount or 300mm Maintenance Bypass Panel to complete your power protection solution. Please click here for Classic Battery Cabinet runtime information. Suitable for small to medium data centers or individual zones of large data centers.

Includes : Network Management Card , Start-Up Service , User Manual

Symmetra PX 128kW Scalable to 160kW, without Bypass, Distribution, or Batteries, 400V

A high-efficiency, modular 3-phase UPS that offers internal redundancy for your data center requirements. With scalable power, this UPS grows with your data center up to 160kW/kVA. Pair with the Classic Battery Cabinet and the Wall-Mount or 300mm Maintenance Bypass Panel to complete your power protection solution. Please click here for Classic Battery Cabinet runtime information. Suitable for small to medium data centers or individual zones of large data centers.

Call for More Information
44553010
Includes: Network Management Card , Start-Up Service , User Manual

SY128K160H-NB Features

Symmetra PX 128kW Scalable to 160kW, without Bypass, Distribution, or Batteries, 400V

  • LCD display
    Alpha-Numeric Display which displays system parameters and alarms.

Symmetra PX Features & Benefits

  • SmartSlot
    Customize UPS capabilities with management cards.
  • Programmable frequency
    Ensures compatibility with different input frequencies.
  • Scalable power capacity
    Reduces UPS over-sizing costs today by allowing quick power upgrades, within the same footprint, later.
  • 5x8 Start-up service included
    Required for full coverage of factory warranty
  • Generator compatible
    Ensures clean, uninterrupted power to protected equipment when generator power is used.
  • Input power factor correction
    Minimizes installation costs by enabling the use of smaller generators and cabling.
  • Fully-rated power kVA equals kW
    Reduces cost by eliminating the need for an oversized UPS for Power Factor Corrected (PFC) loads.
  • Automatic internal bypass
    Supplies utility power to the connected loads in the event of a UPS power overload or fault.
  • Network manageable
    Provides remote power management of the UPS over the network.
  • Configurable for N+1 internal redundancy
    Provides high availability through redundancy by allowing configuration with one more Power Module than is necessary to support the connected load.
  • Modular design
    Provides fast serviceability and reduced maintenance requirements via self-diagnosing, field-replaceable modules.
  • Swappable power modules
    Allows quick addition of power capacity or replacement of existing power modules. Installed modules are automatically recognized by the system.
  • Power Modules connected in parallel
    Enhances availability by allowing immediate, seamless recovery from isolated module failures.
  • Redundant Intelligence Modules
    Provides higher availability to the UPS connected loads by giving redundant communication paths to critical UPS functions.
  • Scalable power capacity
    Reduces UPS over-sizing costs today by allowing quick power upgrades, within the same footprint, later.
  • Power Modules connected in parallel
    Enhances availability by allowing immediate, seamless recovery from isolated module failures.
  • Modular design
    Provides fast serviceability and reduced maintenance requirements via self-diagnosing, field-replaceable modules.
  • Fully-rated power kVA equals kW
    Reduces cost by eliminating the need for an oversized UPS for Power Factor Corrected (PFC) loads.
  • Network manageable
    Provides remote power management of the UPS over the network.
  • User-replaceable batteries
    Increases availability by allowing a trained user to perform upgrades and replacements of the batteries reducing Mean Time to Repair (MTTR)
  • User-replaceable power modules
    Enables simple upgrades and replacements of the Power Modules.
  • Battery modules connected in parallel
    Delivers higher availability through redundant batteries.
  • Configurable for N+1 internal redundancy
    Provides high availability through redundancy by allowing configuration with one more Power Module than is necessary to support the connected load.
  • Generator compatible
    Ensures clean, uninterrupted power to protected equipment when generator power is used.
  • Integrates with StruxureWare Data Center Expert
    An IT-ready, scalable access monitoring system that collects, organizes, and distributes critical alerts, surveillance video and key information, providing a unified view of complex physical infrastructure environments from anywhere on the network
  • Audible alarms
    Provides notification of changing utility power and UPS power conditions
  • LED status indicators
    Quickly understand unit and power status with visual indicators.
  • ENERGY STAR for UPS
    Establishes that the efficiency of the UPS is in the top 25% of the market as verified by third party testing
  • EU CoC for UPS
    Ensures that UPSs sold in the EU are highly efficient
Product Distribution
Product Distribution

Andorra , United Arab Emirates , Antigua and Barbuda , Anguilla , Albania , Armenia , Netherlands Antilles , Angola , Argentina , Austria , Australia , Aruba , Azerbaijan , Bosnia and Herzegovina , Barbados , Belgium , Burkina Faso , Bulgaria , Bahrain , Burundi , Benin , Bermuda , Bolivia , Brazil , Bahamas , Botswana , Belarus , Belize , The Democratic Republic Of Congo , Central African Republic , Congo , Switzerland , Côte d'Ivoire , Chile , Cameroon , China , Colombia , Costa Rica , Serbia and Montenegro , Cuba , Cyprus , Czech Republic , Germany , Djibouti , Denmark , Dominica , Dominican Republic , Algeria , Ecuador , Estonia , Egypt , Western Sahara , Eritrea , Spain , Ethiopia , Finland , Falkland Islands , France , Gabon , United Kingdom , Grenada , Georgia , French Guiana , Ghana , Gibraltar , Gambia , Guinea , Guadeloupe , Equatorial Guinea , Greece , Guatemala , Guyana , Hong Kong , Honduras , Croatia , Haiti , Hungary , Ireland , Israel , Iraq , Iran , Iceland , Italy , Jamaica , Jordan , Kenya , Saint Kitts And Nevis , Kuwait , Cayman Islands , Kazakhstan , Lebanon , Saint Lucia , Liechtenstein , Liberia , Lesotho , Lithuania , Luxembourg , Latvia , Morocco , Moldova , Madagascar , Macedonia , Mali , Mongolia , Martinique , Mauritania , Malta , Mauritius , Malawi , Mexico , Mozambique , Namibia , Niger , Nigeria , Nicaragua , Netherlands , Norway , New Zealand , Oman , Panama , Peru , Pakistan , Poland , Puerto Rico , Portugal , Paraguay , Qatar , Reunion , Romania , Russia , Rwanda , Saudi Arabia , Sudan , Sweden , Slovenia , Slovakia , Sierra Leone , Senegal , Somalia , Suriname , El Salvador , Turks And Caicos Islands , Chad , Togo , Tajikistan , Turkmenistan , Tunisia , Turkey , Trinidad and Tobago , Taiwan , Tanzania , Ukraine , Uganda , Uruguay , Uzbekistan , Saint Vincent And The Grenadines , Venezuela , U.S. Virgin Islands , XF , Yemen , Mayotte , South Africa , Zambia , Zimbabwe

Print Technical Specification

Output

  • Output power capacity
    128.0 KWatts / 128.0 kVA
  • Max Configurable Power (Watts)
    160.0 KWatts / 160.0 kVA
  • Nominal Output Voltage
    230V , 400V 3PH
  • Neutral Output Current
    320A
  • Output Voltage Note
    Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
  • Efficiency at Full Load
    95.0 %
  • Output Voltage Distortion
    Less than 2%
  • Output Frequency (sync to mains)
    50/60 Hz +/- 3 Hz user adjustable +/- 0.1
  • Output Frequency (not synced)
    50Hz +/- 0.1% for 50Hz nominal
  • Topology
    Double Conversion Online
  • Waveform type
    Sine wave
  • Overload Operation
    10 minutes @ 125% and 60 seconds @ 150%
  • Output Voltage THD
    < 2% for 0 to 100% linear load and < 5% for full non linear load
  • Output Voltage Tolerance
    +/-1% static and +/- 5% at 100% load step
  • Bypass
    Built-in Static Bypass

Input

  • Nominal Input Voltage
    400V 3PH
  • Input frequency
    40 - 70 Hz
  • Input Connections
    Hard Wire 5-wire (3PH + N + G)
  • Input voltage range for main operations
    340 - 477V
  • Efficiency at Full Load
    95.0 %
  • Input Total Harmonic Distortion
    Less than 5% for full load
  • Maximum Short Circuit Withstand (Icw)
    30.0kAmps
  • Maximum Input Current
    236.0A
  • Input Power Factor at Full Load
    0.99

Batteries & Runtime

  • Battery type
    No internal battery - uses external battery system
  • Replacement Battery
    SYPBV96K160H
  • Efficiency in Battery Operation
    94.0 %

Communications & Management

  • Interface Port(s)
    DB-9 RS-232 , SmartSlot
  • Control panel
    Multi-function LCD status and control console
  • Audible Alarm
    Alarm when on battery : distinctive low battery alarm : configurable delays
  • Emergency Power Off (EPO)
    Yes
  • Available SmartSlot™ Interface Quantity
    2

Physical

  • Maximum Height
    1991mm , 199.1CM
  • Maximum Width
    600mm , 60.0CM
  • Maximum Depth
    1070mm , 107.0CM
  • Rack Height
    42U
  • Net Weight
    553.0KG
  • Shipping weight
    610.0KG
  • Shipping Height
    2140mm , 214.0CM
  • Shipping Width
    848mm , 84.8CM
  • Shipping Depth
    1210mm , 121.0CM
  • Color
    Black

Environmental

  • Operating Temperature
    0 - 40 °C
  • Operating Relative Humidity
    0 - 95 %
  • Operating Elevation
    0-999.9meters
  • Storage Temperature
    -15 - 40 °C
  • Storage Relative Humidity
    0 - 95 %
  • Storage Elevation
    0-15000meters
  • Audible noise at 1 meter from surface of unit
    63.0dBA
  • Online thermal dissipation
    22992.0BTU/hr
  • Protection Class
    NEMA 1, IP 20

Conformance

  • Approvals
    EN 50091-1, EN/IEC 62040-1-1, EN/IEC 62040-2, EN/IEC 62040-3, ISO 14001, ISO 9001, VFI-SS-111
  • Standard warranty
    1 year on-site repair or replace with factory authorized Start-Up

General

  • Bypass Connection
    5 wire (3PH + N + G)
  • Bypass Protection Device
    250.0
  • Max Bypass Input Current
    250.0A
Manuals and Warranties
Title
Size
Updated On
PDF

Size

1096KB

Updated On

2018-06-18

Schneider Electric Important Safety Instructions in English, Chinese Simplified, French, German, European Spanish, Italian, Russian, Portuguese Brazilian, Dutch, Japanese and Korean
PDF

Size

10361KB

Updated On

2018-06-12

Providing the certified electrician with information on how to install and connect the Symmetra PX 96 and 160 kW UPS
PDF

Size

111KB

Updated On

2018-06-12

Symmetra PX 48-160 kW Release Note
Brochure
Title
Size
Updated On
PDF

Size

1075KB

Updated On

2018-06-06

Features, design description, and technical specifications of the Symmetra PX 96/160
Design/Configuration
Title
Size
Updated On
PDF

Size

9412KB

Updated On

2018-07-30

Providing information on technical data, facility planning, drawings, and options
Agency Approvals
Title
Size
Updated On
PDF

Size

519KB

Updated On

2018-06-13

EU Declaration of Conformity
PDF

Size

79KB

Updated On

2018-06-12

Certificate of Origin
Title
Size
Updated On
Symmetra PX-ET 160kW, Single-Line Diagrams
Symmetra PX-ET 160kW, Mechanicals
BIM Models, UPS, Symmetra PX, 160kW

Firmware Upgrades

Firmware Upgrades
Part Number
Updated On

Part Number

SFSY3P650

Updated On

2017-08-10
AP9630 (CH) Network Management Card, AP9631 (CH) Network Management Card, AP9635 (CH) Network Management Card
Wizards and Configurators
Part Number
Updated On

Part Number

SFDIPW503

Updated On

2018-04-12
UPS Network Management Cards
Part Number
Updated On

Part Number

SFSYPX2377_390

Updated On

2015-07-29

Category

Sub-Category


Scheduling Upgrade to 7X24 for MPRS

Go from OUTDATED to UPGRADED. It's time to update or renovate your aging 3-phase UPS or cooling system. Extending its lifespan can reduce costs and boost uptime!

UPS Communications Cable Smart Signalling 6'/2m - DB9 to RJ45

UPS Cables that provide dedicated connections between APC UPSs and desktops, workstations, and servers

UPS Communications Cable Smart Signalling 15' / 4.5m - DB9 to RJ45

UPS Cables that provide dedicated connections between APC UPSs and desktops, workstations, and servers

Modular UPS Revitalization Service Kit for (1) SYPX 160k Frame with 11 X SYPM10K16H

Go from OUTDATED to UPGRADED. It's time to update or renovate your aging 3-phase UPS or cooling system. Extending its lifespan can reduce costs and boost uptime!

Modular UPS Revitalization Service Kit for (1) SYPX 160k Frame with 10 X SYPM10K16H

Go from OUTDATED to UPGRADED. It's time to update or renovate your aging 3-phase UPS or cooling system. Extending its lifespan can reduce costs and boost uptime!

APC Symmetra PX 96/160kW Value Battery Cabinet with Classical Batteries A

A compact classic battery cabinet for the Symmetra PX 96/160 UPS. Please <a href="http://www.apc.com/wp?dc=3"> click here </a> for additional runtime information.

APC Symmetra PX 96/160kW Value Battery Cabinet with Classical Batteries B

A compact classic battery cabinet for the Symmetra PX 96/160 UPS. Please <a href="http://www.apc.com/wp?dc=3"> click here </a> for additional runtime information.

Advanced Operator Training for Symmetra PX 20 - 80

Get the most from your Schneider Electric solution while learning from our industry proven professionals. Increase your knowledge and confidence operating your data center and managing your facility's physical infrastructure.


Show results per page

Related Products, Accessories & Services

View all accessories and replacement batteries for this product