MGE Galaxy 3000 10kVA 600V-208V

MGE Galaxy 3000 10kVA 600V-208V Front Left
MGE Galaxy 3000 10kVA 600V-208V Front Left
MGE Galaxy 3000 10kVA 600V-208V Front Left
MGE Galaxy 3000 10kVA 600V-208V Front Left
MGE Galaxy 3000 10kVA 600V-208V Miscellaneous
MGE Galaxy 3000 10kVA 600V-208V Miscellaneous
MGE Galaxy 3000 10kVA 600V-208V Front Left
MGE Galaxy 3000 10kVA 600V-208V Front Left
MGE Galaxy 3000 10kVA 600V-208V Miscellaneous
MGE Galaxy 3000 10kVA 600V-208V Miscellaneous
  • Adaptable 3 phase power protection to meet the unique requirements of small data centers and building critical applications

  • Includes: Installation guide, User Manual

View Product Overview

GLTT10KL Features

Key Features

Run time for load W
Run time for load
Enter the total load (power draw) of all devices to be protected by the UPS here. Based on the value entered we will estimate the run time that you will have during a total power outage. Adding run time increases availability by allowing the system to operate through longer outages without shutting down.

The total load (power draw) entered exceeds the maximum value for this product (8000W)

Please enter load to see estimated run time

Max. Capacity Used
Max. Capacity Used
The maximum percentage of UPS capacity used to support your specified load.

Please enter load to see calculated "Max. Capacity Used"

Output power capacity
8.0kWatts / 10.0kVA
Nominal Output Voltage
208V 3PH
Nominal Input Voltage
600V 3PH
Input Connections
Hard Wire 5-wire (3PH + N + G)
Maximum Input Current
28.0A
MGE Galaxy 3000 10kVA 600V-208V
Adaptable 3 phase power protection to meet the unique requirements of small data centers and building critical applications
Includes: Installation guide, User Manual
  • Audible alarms
    Provides notification of changing utility power and UPS power conditions
  • Automatic internal bypass
    Supplies utility power to the connected loads in the event of a UPS power overload or fault.
  • Front-access servicing
    Simplifies installation and UPS maintenance while minimizing space requirements.
  • Generator compatible
    Ensures clean, uninterrupted power to protected equipment when generator power is used.
  • LCD graphics display
    Text and mimic diagrams that display modes of operation, system parameters and alarms.
  • LED status indicators
    Quickly understand unit and power status with visual indicators.
  • Manual maintenance bypass
    Reduces installation costs by eliminating the need for an external mechanical bypass.
  • Network manageable
    Most models provide remote power management options of the UPS over the network. Many do not have NMC embedded.

MGE Galaxy 3000 Features & Benefits

Total Cost of Ownership

Fully-rated power kVA equals kW
Reduces cost by eliminating the need for an oversized UPS for Power Factor Corrected (PFC) loads.
Input power factor correction
Minimizes installation costs by enabling the use of smaller generators and cabling.

Serviceability

Multiple levels of service
With the option of packages or individual service components, our services are structured to allow you to pick and choose what you would like APC to do for you.
Technical support
Our experienced technical support engineers are available to answer your questions, giving you peace of mind knowing the help you need is there when you need it.
Front-access servicing
Simplifies installation and UPS maintenance while minimizing space requirements.

Availability

Network manageable
Most models provide remote power management options of the UPS over the network. Many do not have NMC embedded.
Parallel-redundant capable
Power the connected equipment with multiple uninterruptible power supplies to increase system redundancy
SmartSlot
Customize UPS capabilities with management cards.
Dual mains input
Increases availability by allowing the UPS to be connected to two separate power sources.
Automatic internal bypass
Supplies utility power to the connected loads in the event of a UPS power overload or fault.

Product Distribution

Antigua and Barbuda, Anguilla, Netherlands Antilles, Argentina, Aruba, Barbados, Bermuda, Bolivia, Brazil, Bahamas, Belize, Canada, Chile, Colombia, Costa Rica, Cuba, Dominica, Dominican Republic, Ecuador, Falkland Islands, Grenada, Guadeloupe, Guatemala, Guyana, Honduras, Haiti, Jamaica, Saint Kitts And Nevis, Cayman Islands, Saint Lucia, Martinique, Mexico, Nicaragua, Panama, Peru, Puerto Rico, Paraguay, El Salvador, Turks And Caicos Islands, Trinidad and Tobago, United States, Uruguay, Saint Vincent And The Grenadines, Venezuela, U.S. Virgin Islands

Output

Max Configurable Power (Watts)
8.0kWatts / 10.0kVA
Efficiency at Full Load
85.0 %
Output Voltage Distortion
Less than 3%
Output Frequency (sync to mains)
60 Hz
Output Frequency (not synced)
60Hz +/- 0.1% for 60Hz nominal
Topology
Double Conversion Online
Waveform type
Sine wave
Overload Operation
60 seconds @ 130% and 30 seconds @ 145%
Output Voltage Tolerance
+/-1% static and +/- 5% at 100% load step
Bypass
Built-in Maintenance Bypass, Built-in Static Bypass

Input

Input frequency
60 Hz +/- 3 Hz
Input voltage range for main operations
166 - 239V
Efficiency at Full Load
85.0 %
Input Total Harmonic Distortion
Less than 3% for full load
Type of Input Protection Required
3-pole breaker
Input Power Factor at Full Load
0.98

Batteries & Runtime

Battery type
VRLA
Nominal Battery Voltage
240V
Expected Battery Life (years)
5 - 10
Efficiency in Battery Operation
95.0 %

Communications & Management

Control panel
Multi-function LCD status and control console
Emergency Power Off (EPO)
Yes
Available SmartSlot™ Interface Quantity
2

Physical

Maximum Height
1585MM, 158.5CM
Maximum Width
833MM, 83.3CM
Maximum Depth
1019MM, 101.9CM
Net Weight
1165.91KG
Shipping weight
1188.64KG
Shipping Height
1737MM, 173.7CM
Shipping Width
935MM, 93.5CM
Shipping Depth
1120MM, 112.0CM
Color
Light grey

Environmental

Operating Temperature
0 - 40 °C
Operating Relative Humidity
0 - 95 %
Operating Elevation
0-999.9meters
Storage Temperature
-20 - 45 °C
Storage Relative Humidity
0 - 95 %
Storage Elevation
0-12000meters
Audible noise at 1 meter from surface of unit
69.0dBA
Online thermal dissipation
28000.0BTU/hr

Conformance

Approvals
cUL Listed, FCC Part 15 Class A, UL 1778
Standard warranty
1 year repair or replace

Options

Services