APC AV 1.5kVA S Type Power Conditioner with Battery Backup 120V

APC AV 1.5kVA S Type Power Conditioner with Battery Backup 120V Front Left
APC AV 1.5kVA S Type Power Conditioner with Battery Backup 120V Front Left
APC AV 1.5kVA S Type Power Conditioner with Battery Backup 120V Front Left
APC AV 1.5kVA S Type Power Conditioner with Battery Backup 120V Front Left
APC AV 1.5kVA S Type Power Conditioner with Battery Backup 120V Back
APC AV 1.5kVA S Type Power Conditioner with Battery Backup 120V Back
APC AV 1.5kVA S Type Power Conditioner with Battery Backup 120V Miscellaneous
APC AV 1.5kVA S Type Power Conditioner with Battery Backup 120V Miscellaneous
APC AV 1.5kVA S Type Power Conditioner with Battery Backup 120V Miscellaneous
APC AV 1.5kVA S Type Power Conditioner with Battery Backup 120V Front Left
APC AV 1.5kVA S Type Power Conditioner with Battery Backup 120V Front Left
APC AV 1.5kVA S Type Power Conditioner with Battery Backup 120V Back
APC AV 1.5kVA S Type Power Conditioner with Battery Backup 120V Back
APC AV 1.5kVA S Type Power Conditioner with Battery Backup 120V Miscellaneous
APC AV 1.5kVA S Type Power Conditioner with Battery Backup 120V Miscellaneous
APC AV 1.5kVA S Type Power Conditioner with Battery Backup 120V Miscellaneous
  • Audio-video power protection from blackouts, voltage sags & swells, electrical noise interference and damaging power transients

  • Includes: Battery modules ship installed, Cat 6 Ethernet cable, CD with software, Country-specific detachable power cord, Rack mounting brackets, Rack mounting support ...

View Product Overview

S15 Features

Key Features

Run time for load
Min-max
W
Run time for load
Enter the total load (power draw) of all devices to be protected by the UPS here. Based on the value entered we will estimate the run time that you will have during a total power outage. Adding run time increases availability by allowing the system to operate through longer outages without shutting down.

The total load (power draw) entered exceeds the maximum value for this product (1000 W)

Please enter load to see estimated run time

The total load (power draw) entered is less than the minimum value for this product ({} W)

Max. Capacity Used
Max. Capacity Used
The maximum percentage of UPS capacity used to support your specified load.

Please enter load to see calculated "Max. Capacity Used"

Output power capacity
1.0kWatts / 1.44kVA
Rack Height
3U
Output Connections
(12) NEMA 5-15R (Battery Backup)
Nominal Output Voltage
120V
Nominal Input Voltage
120V
Input Connections
NEMA 5-15P
Maximum Input Current
12.0A
APC AV 1.5kVA S Type Power Conditioner with Battery Backup 120V
Audio-video power protection from blackouts, voltage sags & swells, electrical noise interference and damaging power transients
Includes: Battery modules ship installed, Cat 6 Ethernet cable, CD with software, Country-specific detachable power cord, Rack mounting brackets, Rack mounting support rails, USB cable, User manual

AV Power Conditioners & Battery Backups Features & Benefits

Protection

Safety-agency approved
Ensures the product has been tested and approved to work safely with the connected service provider equipment and within the specified environment.
Isolated power filter banks
Eliminates electromagnetic and radio frequency interference (EMI/RFI) as a source of audio-video signal degradation.
Power conditioning
Protects connected loads from surges, spikes, lightning, and other power disturbances.
Boost and Trim Automatic Voltage Regulation (AVR). (Does not apply to J25B)
Eliminates voltage fluctuations as a source of AV signal degradation and component power-supply stress.
Dataline surge protection
Provides protection of connected equipment from power surges on the data lines.

Serviceability

Resettable circuit breakers
Enables a quick recovery from overload events.
Multiple mounting methods
Allows for standardization on one product for use in different environments.
Front-access servicing
Simplifies installation and UPS maintenance while minimizing space requirements.

Manageability

LED & display dimmer
Adjust the unit's LED and display brightness independently of each other to suit your individual tastes and environment.
Adjustable voltage sensitivity
Provides the ability to adapt the UPS for optimal performance in specific power environments or generator applications.
Sequenced turn on/off
Helps power on components in the proper order to prevent speaker stress. Proper sequencing can also help manage current draw on startup to prevent unnecessary circuit breaker tripping.

Product Distribution

Brazil, Canada, United States

Technical Specifications

Output

Max Configurable Power (Watts)
1.0kWatts / 1.44kVA
Output Frequency (sync to mains)
50/60 Hz +/- 3 Hz Sync to mains
Topology
Line interactive
Waveform type
Sine wave
Maximum Output Current
12
Transfer Time
2-4 ms
Transfer Time
7 ms typical

Input

Input frequency
50/60 Hz +/- 3 Hz Auto-sensing
Input voltage range for main operations
90 - 140V
Number of Power Cords
1
Transfer Time
2-4 ms

Batteries & Runtime

Battery type
Lead-acid battery
Typical recharge time
8hour(s)
Replacement Battery
Expected Battery Life (years)
3 - 5
RBC Quantity
1
Battery Charge Power (Watts)
37 Watts
Extendable Run Time
1

Communications & Management

Control panel
Multifunction LCD status and control console
Audible Alarm
Audible and visible alarms : configurable delays

Surge Protection and Filtering

Surge energy rating
4080Joules
Data Line Protection
Cable modem/video protection, Coaxial 2-way splitter with protection, Coaxial video/cable protection, RJ45 10/100/1000 Base-T Ethernet protection, RJ45 modem/fax protection (four wire dual line)
Filtering
Full time multi-pole noise filtering : 0.7% IEEE surge let-through : zero clamping response time : meets UL 1449

Physical

Maximum Height
133MM, 13.3CM
Maximum Width
432MM, 43.2CM
Maximum Depth
483MM, 48.3CM
Net Weight
28.18KG
Shipping weight
34.55KG
Shipping Height
335MM, 33.5CM
Shipping Width
513MM, 51.3CM
Shipping Depth
594MM, 59.4CM
Color
Silver
Master Carton Units
1.0
Units per Pallet
12.0
SCC Codes
107313040

Environmental

Operating Temperature
0 - 40 °C
Operating Relative Humidity
5 - 95 %
Operating Elevation
0 - 3048meters
Storage Temperature
-15 - 45 °C
Storage Elevation
0 - 15240meters

Conformance

Approvals
CSA, FCC part 15 class B, UL 1778
Equipment protection policy
Unlimited lifetime
Standard warranty
2 years repair or replace

Options

Services