InRow RC, 300mm, Chilled Water, 208-230V, 50/60Hz - HT
-
Close-coupled, chilled water cooling for medium to large data centers
-
Includes: Installation guide, Operations and maintenance manual
ACRC301H Features
Key Features
Rack Height
42U
Input Connections
Hard wire 3-wire
InRow RC, 300mm, Chilled Water, 208-230V, 50/60Hz - HT
Close-coupled, chilled water cooling for medium to large data centers
Includes: Installation guide, Operations and maintenance manual
-
Active Airflow Control
Monitors and actively adjust cooling unit airflow in containment systems, while providing visibility to effective cooling to critical IT equipment.
-
Dew point monitoring
Prevents condensation from forming inside the enclosure by dissuading access when the external dew point is above supply air temperature.
-
Hot swappable fans
Allows system to remain operational if a fan replacement is required.
-
Leak detection
Notifies user in the event of a water leak within the coiling unit.
-
Top and bottom chilled water connections
Provide flexibilty in installation based on the constraints of a given area.
-
Washable filters
Easy to maintain, cleanable, deep loading mesh filter removes particles from the return air stream.
Uniflair Chilled Water InRow Cooling Features & Benefits
Total cost of Ownership
Row-based architecture
Captures hot exhaust air directly from the IT equipment, thereby increasing the unit's sensible cooling capacity over traditional cooling architectures.
Variable speed fans
Variable speed fans reduce energy consumption during off-peak cooling periods.
Serviceability
Easy service access
Allows for all serviceable components to be replaced/maintained by easily accessible panels/doors.
Manageability
Building management system integration
Send alarms and data points allowing you to manage critical building infrastructure from a single system.
Microprocessor controller
Provides proactive control and real-time monitoring via a four line, eighty character, alphanumeric display.
Real-Time capacity monitoring
Real-time display of current and available cooling.
Availability
Active response controls
Monitors and actively adjusts cooling capacity to ensure proper server inlet temperatures. Through the microprocessor controller, visibility into the operation and health of the unit is provided.
Dual A-B power inputs
Draws power from the UPS for power protection with dual feeds for redundancy.
Top and bottom chilled water connections
Allows chilled water to be connected from the top, if routing from overhead, or bottom, if on a raised floor.
Predictable cooling
Placing the unit in the row of racks moves the source of cooling closer to the heat load. This eliminates air mixing and provides a predictable cooling architecture.
Rack inlet control
Rack inlet control guarantees inlet temperature to IT equipment.
Agility
Casters
Provides flexibility to move the unit to wherever cooling is required.
Modular design
Modular design provides scalable solutions to add cooling as demand increases.
Scalable densities
Allows for higher densities to be achieved by integrating containment with room, row and rack cooling system architectures.
Product Distribution
United Arab Emirates, Afghanistan, Albania, Armenia, Angola, Argentina, Austria, Australia, Azerbaijan, Bosnia and Herzegovina, Belgium, Burkina Faso, Bulgaria, Bahrain, Burundi, Benin, Brazil, Botswana, Belarus, Canada, Switzerland, Côte d'Ivoire, Chile, Cameroon, China, Costa Rica, Cyprus, Czech Republic, Germany, Djibouti, Denmark, Algeria, Estonia, Egypt, Eritrea, Spain, Ethiopia, Finland, Fiji, France, Gabon, United Kingdom, Georgia, Ghana, Gambia, Greece, Hong Kong, Croatia, Hungary, Indonesia, Ireland, Israel, India, Iraq, Iceland, Italy, Jordan, Japan, Kenya, Cambodia, South Korea, Kuwait, Cayman Islands, Kazakhstan, Lebanon, Liberia, Lithuania, Luxembourg, Latvia, Morocco, Macedonia, Mali, Myanmar, Mongolia, Mauritania, Malta, Malaysia, Mozambique, Namibia, Nigeria, Netherlands, New Zealand, Oman, Philippines, Pakistan, Poland, Portugal, Romania, Russia, Rwanda, Sweden, Singapore, Slovenia, Slovakia, Sierra Leone, Senegal, Somalia, Suriname, Togo, Thailand, Tajikistan, Turkmenistan, Turkey, Taiwan, Tanzania, Ukraine, Uganda, United States, Uzbekistan, Vietnam, Yemen, South Africa, Zambia, Zimbabwe
Input
Input frequency
50/60 Hz
Number of Power Cords
2
Power Feeds
2.0
Input Power
1900 Watts
Maximum Overcurrent Protection
15.0A
Minimum Circuit Amp Capacity
15.0
Communications & Management
Control panel
Multifunction LCD status and control console
Audible Alarm
Audible and visible alarms prioritized by severity
Physical
Maximum Height
1991MM, 199.1CM
Maximum Width
300MM, 30.0CM
Maximum Depth
1095MM, 109.5CM
Net Weight
210.0KG
Shipping weight
220.0KG
Shipping Height
2118MM, 211.8CM
Shipping Width
746MM, 74.6CM
Shipping Depth
1137MM, 113.7CM
Color
Black
Units per Pallet
1.0
Conformance
Approvals
C-Tick, CE, EN 55022 class A, EN 55024, EN 60950, GOST, IEC 60950, IEC 61000-3-2, IEC 61000-3-3, MEA, VDE
Standard warranty
1 year (parts only)
Sustainable Offer Status
RoHS
Compliant
Proposition 65 Warning
Available in Documentation tab
General
Air Discharge Patterns
Horizontal
Air Flow
1982.18lps
Intake Air
Rear return
Minimum Water Inlet Temperature
7.0 °C