{"support":{"yesButton":"Да","noButton":"Нет","feedback":{"title":"Что мы можем сделать лучше?"},"submitButton":"Отправить","successMessage":"Благодарим вас за отзыв","title":"Было ли это полезно?","feedbackPercentLabel":"пользователей считают это полезным","captcha":{"error":"Установите флажок"}}}
Поиск часто задаваемых вопросов
{"searchBar":{"inputPlaceholder":"Выполните поиск по ключевому слову или задайте вопрос","searchBtn":"Поиск","error":"Введите ключевое слово для поиска"}}
InRow Entering Fluid Temp threshold is not alarming
Issue:
InRow Entering Fluid Temp threshold is not alarming
Product line:
InRow
Environment:
Data Center Cooling
Cause:
Resolution:
In the newest firmware ACRC 372 and higher the entering fluid temp alarm threshold violation will not be reported unless two conditions are met. The unit has a >=40% valve position opening, and the entering temperature is above the threshold.
InRow Entering Fluid Temp threshold is not alarming
Product line:
InRow
Environment:
Data Center Cooling
Cause:
Resolution:
In the newest firmware ACRC 372 and higher the entering fluid temp alarm threshold violation will not be reported unless two conditions are met. The unit has a >=40% valve position opening, and the entering temperature is above the threshold.
Узнайте больше
Узнайте больше
Не удается найти то, что нужно?
Обратитесь в нашу службу поддержки клиентов, чтобы получить техническую поддержку, помощь в составлении жалоб и многое другое.