InfrastruXure (ISX) Manager Reports "Bank" Current as "Phase" Current for Certain Rack PDUs
Published date:
18 December 2013
Issue
Bank current is showing as phase current within the InfrastruXure (ISX) Manager data log
Product Line
InfrastruXure (ISX) Manager - AP92200
Rack Power Distribution Unit models:
AP7802
AP7811
AP7822
AP7832
AP7832J
AP7841
AP7853
AP7902
AP7902J
AP7911
AP7922
AP7932
AP7932J
AP7941
AP7853
Environment
All serial numbers
All ISX Manager versions
All Rack PDU firmware versions
Cause
For certain single phase Rack Mount Power Distribution Units with multiple banks of outlets, the ISX Manager will list their current by "phase" instead of by "bank" in the Data Log.
This means that Bank #1 will be listed as "L1" and Bank #2 will be listed as"L2," even though all current is being supplied on the same electrical phase. L3 in the log will be the total current draw from both banks.
All alarms related to this labeling issue will also report the term as phase and not bank. All values reported in the logs are correct apart for the labels (Phase vs Bank).
Resolution
Make note of the labeling discrepancy