{"support":{"yesButton":"yes","noButton":"no","feedback":{"title":"What can we do to improve?"},"submitButton":"Submit","successMessage":"Thank you for your feedback","title":"Did this answer your question?","feedbackPercentLabel":"of people found this helpful","captcha":{"error":"Please tick the box"}}}

Search FAQs

{"searchBar":{"inputPlaceholder":"Search by keyword or ask a question","searchBtn":"Search","error":"Please enter a keyword to search"}}

Modular PDU Breaker LED Light Staying Green or Not Changing State


Issue:
Modular PDU Breaker LED Light Staying Green or Not Changing State

Product line:
Modular PDU

Environment:
Opening and closing of breaker does not change the LED status light on breaker

Cause:
If the Modular PDU Alarm Status if set to Off, the breaker will never change state. So the Green LED will always be lit
->
If the Modular PDU "Alarm Status" and "Position Alarm" is set to Off, the breaker will never change state. So the Green LED will always be lit

Resolution:
In the Web interface of the PDPM, within the settings of each module, the “enable” box needs to be checked so the alarm and LED will trigger.
The “Mass Configuration” option is available only when looking at the “all locations” screen.
->
In the Web interface of the PDPM, within the settings of each module, both “enable” box needs to be checked so the alarm and LED will trigger.