Overview
PresentationA high-performance, 3-phase, modular, scalable, power protection solution with industry-leading efficiency, capacity, and performance for medium to large data centers and mission critical environments.
Lead timeUsually Ships within 6 Weeks
Main
Main Input Voltage480 V 3 phases
400 V 3 phases
Other Input Voltage415 V
Main Output Voltage480 V 3 phases
400 V 3 phases
Other Output Voltage415 V
Rated power in W125000 W
Rated power in VA125000 VA
Output connector typeHard wire 4-wire (3P + E) 1
Hard wire 5-wire (3P + N + E) 1
Battery typeExternal battery system
Provided equipmentAssembly service
Installation guide
Start-up service
User manual
Web/SNMP management card
General
Bypass voltage tolerance+/- 10 % settable from +/- 4/6/8 and 10 %
Number of power module free slots5
Number of power module filled slots5
RedundantYes
Physical
ColourBlack
Height199.1 cm
Width160 cm
Depth107 cm
Net weight1227 kg
USB compatibleNo
Input
Network frequency40...70 Hz auto-sensing
Number of input connectors1 hard wire 4-wire (3P + E)
1 hard wire 5-wire (3P + N + E)
Input voltage limits408...552 V 480 V
Max short time withstand current50 kA
Input harmonic distortionLess than 5 % for full load
Input protection type3-pole circuit breaker
Load power factor0.5 leading to 0.5 lagging
Input Power Factor at Full Load0.99
Output
Maximum configurable power in W250000 W
Harmonic distortionLess than 2 %
Output frequency50 Hz sync to mains
60 Hz +/- 0.1 % for 60 Hz nominal unsynchronised
50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised
60 Hz sync to mains
UPS typeDouble conversion online
Wave typeSine wave
Output voltage tolerance+/- 1% static and +/- 5% at 100% load step
Output harmonic distortion< 2% linear load and < 3% non-linear load
Output overload operation10 minutes at 125% and 60 seconds at 150%
Bypass typeBuilt-in maintenance bypass
Built-in static bypass
Efficiency96 % (in battery operation)
Maximum configurable power in VA500000 VA
Transfer time2 ms typical
Conformance
Product certificationscUL listed
UL listed
StandardsCSA C22.2 No 107.3-05
EN/IEC 62040-1-1
EN/IEC 62040-2
EN/IEC 62040-3
OSHPD
UL 1778
UL 60950-1
Environmental
Ambient air temperature for operation0…40 °C
Relative humidity0…95 %
Operating altitude0...3333 ft
Ambient air temperature for storage-30…70 °C
Storage Relative Humidity0…95 %
Storage altitude0.00…15240.00 m
Acoustic level54 dBA
heat dissipation15473 Btu/h
NEMA degree of protectionNEMA 1
IP degree of protectionIP20
Batteries & Runtime
EfficiencyView Efficiency Graphaction_new_window
Number of battery free slots0
Battery power in VAH0 VAh runtime
Extended runtime1
Communications & Management
Free slots1
Preinstalled deviceNetwork management card 2 with environmental monitoring, out of band access and Modbus
control panelTouch screen LCD user interface
Emergency power offOptional
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height215 cm
Package 1 Width127 cm
Package 1 Length187 cm
Package 1 Weight1377 kg
Contractual warranty
Warranty1 year on-site repair or replace with factory authorized Start-Up
arrow2_down

Sustainability

Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-class environmental performance. Green Premium promises compliance with the latest regulations, transparency on environmental impacts, as well as circular and low-CO2 products.
Learn morearrow2_left
Resource performance

Energy efficient product

notification_ok

EU RoHS Directive

Not compliant

arrow2_down

Documents

arrow2_down

Software and Firmware

Need more information? Check our technical FAQs!

Easily find answers to the most frequently asked questions.