MGE Galaxy 5500 120kVA 400V Single UPS, Start-up 5x8
G55TUPSU120HINS
Discontinued on:05 July 2021
To be end-of-service on:31 December 2030
Specifications
Presentation | A versatile 3-phase UPS for facility, industrial and data center applications. Configurable system with a comprehensive range of accessories to meet your application demands. |
---|---|
Lead time | Usually Ships within 2 Weeks |
Main Input Voltage | 400 V 3 phases |
---|---|
Other Input Voltage | 380 V 415 V |
Main Output Voltage | 400 V 3 phases |
Other Output Voltage | 380 V 415 V |
Rated power in W | 108000 W |
Rated power in VA | 120000 VA |
output connector type | Hard wire 4-wire (3P + E) 1 |
Battery type | External battery system |
provided equipment | Installation guide Network management card Start-up service User manual |
Bypass voltage tolerance | +/- 10 % settable from +/- 4/6/8 and 10 % |
---|---|
Max bypass input current | 173 A |
Number of power module free slots | 0 |
Number of power module filled slots | 0 |
Redundant | No |
Height | 190 cm |
---|---|
Width | 71.2 cm |
Depth | 85.5 cm |
Net weight | 520 kg |
Mounting preference | No preference |
USB compatible | No |
network frequency | 45...65 Hz |
---|---|
number of input connectors | 1 hard wire 4-wire (3P + E) 1 hard wire 4-wire (3P + N) |
input voltage limits | 323...437 V 380 V 340...460 V 400 V 353...477 V 415 V |
Maximum input current | 228 A |
Switching current capacity | 125 A |
Max short time withstand current | 20 kA |
Input harmonic distortion | Less than 5 % for full load |
Input protection type | GL fuse |
Load power factor | 0.9 |
Input Power Factor at Full Load | 1 |
Maximum configurable power in W | 108000 W |
---|---|
Harmonic distortion | Less than 2 % |
output frequency | 50/60 Hz +/- 3 Hz user adjustable +/- 0.1 Hz sync to mains 50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised |
Crest factor | 3 : 1 |
Wave type | Sine wave |
Output voltage tolerance | +/- 1% static and +/- 5% at 100% load step |
Output harmonic distortion | < 1% linear load and < 2.5% non-linear load |
Output overload operation | 10 minutes at 125% and 60 seconds at 150% |
Required output current protection | 173 A |
Bypass type | Built-in maintenance bypass Built-in static bypass Optional external bypass |
Maximum output current | 480 A |
Maximum configurable power in VA | 120000 VA |
product certifications | CE TÜV VDE |
---|---|
Standards | IEC 62040-1-2 EN/IEC 62040-2 EN/IEC 62040-3 ISO 9001 |
Ambient air temperature for operation | 0…40 °C |
---|---|
relative humidity | 0…95 % |
Operating altitude | 0...3333 ft |
Ambient air temperature for storage | -20…45 °C |
storage Relative Humidity | 0…95 % |
Storage altitude | 0.00…12192.00 m |
Acoustic level | 60.2 dBA |
IP degree of protection | IP20 |
Efficiency | View Efficiency Graph |
---|---|
Number of battery filled slots | 0 |
Number of battery free slots | 0 |
Additional information | Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage |
Battery power in VAH | 0 VAh runtime |
Extended runtime | 0 |
Free slots | 2 |
---|---|
Preinstalled device | Network management card 2 with environmental monitoring, out of band access and Modbus |
control panel | Multifunction LCD status and control console |
Emergency power off | Yes |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 203 cm |
Package 1 Width | 96 cm |
Package 1 Length | 98 cm |
Package 1 Weight | 540 kg |
Warranty | 1 year on-site repair or replace with factory authorized Start-Up, 1 year (parts only) |
---|
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-class environmental performance.
Green Premium promises compliance with the latest regulations, transparency on environmental impacts, as well as circular and low-CO2 products.
Learn moreResource performance
Energy efficient product
EU RoHS Directive
Under investigation
Documents
Software and Firmware
Need more information? Check our technical FAQs!
Easily find answers to the most frequently asked questions.