{"support":{"yesButton":"Sí","noButton":"No","feedback":{"title":"¿Qué podemos hacer para mejorar?"},"submitButton":"Enviar","successMessage":"Gracias por tus comentarios","title":"¿Te fue de ayuda?","feedbackPercentLabel":"de las personas encontraron esto útil","captcha":{"error":"Por favor, marca una casilla"}}}

Buscar Preguntas Frecuentes

{"searchBar":{"inputPlaceholder":"Busca por palabra clave o haz una pregunta","searchBtn":"Buscar","error":"Ingresa una palabra para buscar"}}

Why are all LED's flashing simultaneously on my Smart-UPS SU, SUA, or SURT model?


Issue:

LED's flashing simultaneously

Product Line:

Smart-UPS

Environment:

All non-LCD display models (Line Interactive and Online), All Serial Numbers

Cause:

All LED's, or the two center columns of LED's flashing simultaneously generally indicates a hardware failure.

Resolution:

Try to reset the fault by turning the UPS off/on or by performing a "brain dead" on the unit. To perform a "brain dead":
  • Turn off the UPS
  • Unplug the UPS from utility power
  • Press and hold the off button again - You will hear a "click" and may see a brief flash of the LED's
If this fails to clear the fault, contact APC Support for further assistance.