Our Brands

Symmetra PX 16kW All-In-One, Scalable to 48kW, without Batteries, 400V

SY16K48H-PDNB

+ Lifecycle Services

arrow2_down

Specifications

Overview
PresentationScalable power and distribution in a high-density, single-frame design. This high-efficiency 3-phase UPS scales as your data center grows up to 48kW/48kVA. Suitable for small & medium data center applications. To be used with either external third party battery system, or with internal long life modular batteries SYBT9-B4LL.
Lead timeUsually Ships within 3 Weeks
Main
Main Input Voltage400 V 3 phases
Other Input Voltage380 V
400 V
415 V
Main Output Voltage230 V
400 V 3 phases
Other Output Voltage380 V
400 V
415 V
Rated power in W16000 W
Rated power in VA16000 VA
Output connector typeHard wire 5-wire (3P + N + E) 1
Battery typeExternal battery system
Provided equipmentNetwork management card
Start-up service
General
Bypass wiring configuration5 wire (3P + N + E)
Bypass voltage tolerance+/- 10 % settable from +/- 4/6/8 and 10 %
Max bypass input current80 A
Bypass current protection80 A
Number of power module free slots0
Number of power module filled slots0
RedundantNo
Physical
Height199.1 cm
Width60 cm
Depth107 cm
Net weight341 kg
USB compatibleNo
Input
Network frequency40...70 Hz
Number of input connectors1 hard wire 5-wire (3P + N + E)
Input voltage limits340...477 V
Maximum input current33 A
Switching current capacity100 A
Max short time withstand current30 kA
Input harmonic distortionLess than 5 % for full load
Input protection typeGL fuse
Load power factor0.5 leading to 0.5 lagging
Input Power Factor at Full Load0.99
Output
Maximum configurable power in W48000 W
Harmonic distortionLess than 2 %
Output frequency50/60 Hz +/- 3 Hz user adjustable +/- 0.1 Hz sync to mains
50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised
60 Hz +/- 0.1 % for 60 Hz nominal unsynchronised
UPS typeDouble conversion online
Wave typeSine wave
Output voltage tolerance+/- 1% static and +/- 5% at 100% load step
Output harmonic distortion< 2% for 0 to 100% linear load and < 6% for full non-linear load
Output overload operation10 minutes at 125% and 60 seconds at 150%
Required output current protection100 A
Bypass typeBuilt-in static bypass
Maximum configurable power in VA48000 VA
Conformance
StandardsEN 50091-1
EN/IEC 62040-1-1
EN/IEC 62040-2
EN/IEC 62040-3
ISO 14001
ISO 9001
VFI-SS-111
Environmental
Ambient air temperature for operation0…40 °C
Relative humidity0…95 %
Operating altitude0...3333 ft
Ambient air temperature for storage-15…40 °C
Storage Relative Humidity0…95 %
Storage altitude0.00…15240.00 m
Acoustic level61 dBA
Heat dissipation2573 Btu/h
NEMA degree of protectionNEMA 1
Batteries & Runtime
Number of battery filled slots0
Number of battery free slots0
Additional informationConfigurable for 380 : 400 or 415 V 3 Phase nominal output voltage
Battery power in VAH0 VAh runtime
Extended runtime0
Communications & Management
Free slots2
Preinstalled deviceNetwork management card with CAN
Control panelMultifunction LCD status and control console
Emergency power offYes
Packing Units
Unit Type of Package 1Db
Number of Units in Package 11
Package 1 Height214 cm
Package 1 Width121 cm
Package 1 Length84.8 cm
Package 1 Weight368 kg
Contractual warranty
Warranty1 year on-site repair or replace with factory authorized Start-Up
arrow2_down

Sustainability

Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-class environmental performance. Green Premium promises compliance with the latest regulations, transparency on environmental impacts, as well as circular and low-CO2 products.
Learn morearrow2_left

EU RoHS Directive

Not compliant

arrow2_down

Documents

arrow2_down

Software and Firmware

Need more information? Check our technical FAQs!

Easily find answers to the most frequently asked questions.