APC Smart-UPS RT 5000VA, 230V, rackmount, 3U, 8x IEC 60320 C13 & 6x IEC Jumpers & 2x IEC 60320 C19 outlets
SURT5000RMXLI
Discontinued on:31 December 2017
End-of-service on:31 December 2022
Recommended replacement(s)
Replacement battery (1) is available
Specifications
Lead time | Usually in Stock |
---|
Run time for load WEnter the total load (power draw) of all devices that will be protected by the UPS. This will be used to estimate the run time of your devices during a total power outage. Adding run time increases availability by allowing the system to operate through longer outages without shutting down. Min-max: 350-3500 W | |
---|---|
Max. Capacity Used The maximum percentage of UPS capacity used to support your specified load. | |
Main Input Voltage | 230 V |
Other Input Voltage | 220 V 240 V |
Main Output Voltage | 230 V |
Other Output Voltage | 220 V 240 V |
Rated power in W | 3500 W |
Rated power in VA | 5000 VA |
output connection type | 8 IEC 60320 C13 6 IEC Jumpers 2 IEC 60320 C19 |
Number of rack unit | 3U |
Battery type | Lead-acid battery |
Provided equipment | CD with software Rack mounting support rails Smart UPS signalling RS-232 cable User manual Web/SNMP management card |
Number of power module free slots | 0 |
---|---|
Number of power module filled slots | 0 |
Redundant | No |
Colour | Black |
---|---|
Height | 13 cm |
Width | 43.2 cm |
Depth | 66 cm |
Net weight | 54.55 kg |
Mounting location | Front |
Mounting preference | Lower |
Mounting mode | Rack-mounted |
Two post mountable | 0 |
USB compatible | No |
Network frequency | 50/60 Hz +/- 5 Hz auto-sensing |
---|---|
Number of input connectors | 1 hard wire 3-wire |
Input voltage limits | 160...280 V |
Maximum configurable power in W | 3500 W |
---|---|
Harmonic distortion | Less than 3 % |
Output frequency | 50/60 Hz +/- 3 Hz user adjustable +/- 0.1 Hz sync to mains |
Crest factor | 3 : 1 |
UPS type | Double conversion online |
Wave type | Sine wave |
Bypass type | Internal bypass (automatic and manual) |
Efficiency | 92 % (full load) |
Maximum configurable power in VA | 5000 VA |
Product certifications | C-Tick CE GOST VDE |
---|
Ambient air temperature for operation | 0…40 °C |
---|---|
Relative humidity | 0…95 % |
Operating altitude | 0...10000 ft |
Ambient air temperature for storage | -15…45 °C |
Storage Relative Humidity | 0…95 % |
Storage altitude | 0.00…15240.00 m |
Acoustic level | 55 dBA |
heat dissipation | 1040 Btu/h |
Run Time | View Runtime Graph |
---|---|
Number of battery filled slots | 2 |
Battery recharge time | 2.5 h |
Number of battery replacement quantity | 1 |
Additional information | Configurable for 220 : 230 or 240 nominal output voltage |
Battery charger power | 341 W rated |
Battery power in VAH | 855 VAh runtime |
Battery life | 3…5 year(s) |
Replacement battery | APCRBC140 |
Battery option | SURT192RMXLBP 1 2564 VAh SURT192RMXLBP 2 4272 VAh SURT192RMXLBP 3 5981 VAh SURT192RMXLBP 4 7690 VAh SURT192RMXLBP 5 9399 VAh SURT192RMXLBP 6 11107 VAh SURT192RMXLBP 8 14525 VAh SURT192RMXLBP 10 17943 VAh |
Extended runtime | 1 |
Free slots | 0 |
---|---|
Preinstalled device | Network management card with environmental monitoring |
Alarm | Alarm when on battery : distinctive low battery alarm : overload continuous tone alarm |
Emergency power off | Yes |
Surge energy rate | 480 J |
---|---|
Noise suppression | Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449 |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Warranty | 2 years repair or replace, optional on-site warranties available, optional extended warranties available |
---|
Documents
Software and Firmware
Need more information? Check our technical FAQs!
Easily find answers to the most frequently asked questions.
SURT5000RMXLI is replaced by: