Search FAQs

Video: How to clear Humidifier Run Hours on a Chilled Water Uniflair Unit

Issue:
This document provides the steps needed on how to clear Humidifier Run Hours Violation.
 
Product line:
Uniflair: TDCV700X, TDCV1000X, TDCV1200X, TDCV1700X, TDCV2500X, TDCV3400X, TDCV4000X, TDCV4300X, TUCV700X, TUCV1000X, TUCV1200X, TUCV1700X, TUCV2500X, TUCV3400X, TUCV4000X, TUCV4300X, HDCV4500X, HDCV5000X.
 
Environment:
All Serial Numbers.
 
Cause:
Install, Repair.
 
Resolution
 
Press PRG.
 
Use the DOWN arrow to scroll to Hourmeter Settings.
 
Press ENTER.
 
Use the DOWN arrow to scroll to Humidifier Run Hours.
 
Press ENTER twice.
 
Press the DOWN arrow once.
 
Press ENTER again to clear run hours.
 
Press ESC three times to exit back to main menu.

 