The IR RP DX use the R407C fluid, but is it possible to use the R410A instead of R407C for minor impact for the ambient temperatures?

Published date: 16 April 2019

Issue:
The IR RP DX use the R407C fluid, but is it possible to use the R410A instead of R407C for minor impact for the ambient temperatures?
 
Product line:
ACRP100, ACRP101, ACRD500, ACRD501, ACRD600, ACRD601, ACRD600P, ACRD601P
 
Environment:
All Serial Numbers
 
Cause:
Install, Repair
 
Resolution
 
Systems designed for R407C are not designed to hold the much higher pressures of R410A.

This conversion is not possible for any type of unit.


 