Our Brands

Symmetra PX 128kW Scalable to 160kW, without Bypass, Distribution, or Batteries, 400V

SY128K160H-NB

+ Lifecycle Services

arrow2_down

Specifications

Overview
PresentationA high-efficiency, modular 3-phase UPS that offers internal redundancy for your data center requirements. With scalable power, this UPS grows with your data center up to 160kW/kVA. Pair with the Classic Battery Cabinet and the Wall-Mount or 300mm Maintenance Bypass Panel to complete your power protection solution. Please click here for Classic Battery Cabinet runtime information. Suitable for small to medium data centers or individual zones of large data centers.
Lead timeUsually Ships within 3 Weeks
Main
Main Input Voltage400 V 3 phases
Main Output Voltage230 V
400 V 3 phases
Rated power in W128000 W
Rated power in VA128000 VA
Output connector typeHard wire 5-wire (3P + N + E) 1
Battery typeExternal battery system
Provided equipmentNetwork management card
Start-up service
User manual
General
Bypass wiring configuration5 wire (3P + N + E)
Max bypass input current250 A
Bypass current protection250 A
Number of power module free slots2
Number of power module filled slots8
RedundantYes
Physical
ColourBlack
Height199.1 cm
Width60 cm
Depth107 cm
Net weight553 kg
USB compatibleNo
Input
Network frequency40...70 Hz
Number of input connectors1 hard wire 5-wire (3P + N + E)
Input voltage limits340...477 V
Maximum input current236 A
Switching current capacity315 A
Max short time withstand current30 kA
Input harmonic distortionLess than 5 % for full load
Load power factor0.5 leading to 0.5 lagging
Input Power Factor at Full Load0.99
Output
Maximum configurable power in W160000 W
Harmonic distortionLess than 2 %
Output frequency50/60 Hz +/- 3 Hz user adjustable +/- 0.1 Hz sync to mains
50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised
UPS typeDouble conversion online
Wave typeSine wave
Output voltage tolerance+/- 1% static and +/- 5% at 100% load step
Output harmonic distortion< 2% for 0 to 100% linear load and < 5% for full non-linear load
Output overload operation10 minutes at 125% and 60 seconds at 150%
Required output current protection250 A
Neutral output current320 A
Bypass typeBuilt-in static bypass
Efficiency95 % (full load)
95 % (half load)
94 % (in battery operation)
Maximum configurable power in VA160000 VA
Conformance
StandardsEN 50091-1
EN/IEC 62040-1-1
EN/IEC 62040-2
EN/IEC 62040-3
ISO 14001
ISO 9001
VFI-SS-111
Environmental
Ambient air temperature for operation0…40 °C
Relative humidity0…95 %
Operating altitude0...3333 ft
Ambient air temperature for storage-15…40 °C
Storage Relative Humidity0…95 %
Storage altitude0.00…15240.00 m
Acoustic level63 dBA
heat dissipation22992 Btu/h
NEMA degree of protectionNEMA 1
IP degree of protectionIP20
Batteries & Runtime
Additional informationConfigurable for 380 : 400 or 415 V 3 Phase nominal output voltage
Battery power in VAH0 VAh runtime
Extended runtime0
Communications & Management
Free slots2
Preinstalled deviceNetwork management card with CAN
control panelMultifunction LCD status and control console
Emergency power offYes
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height214 cm
Package 1 Width121 cm
Package 1 Length84.8 cm
Package 1 Weight610 kg
Contractual warranty
Warranty1 year on-site repair or replace with factory authorized Start-Up
arrow2_down

Sustainability

Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-class environmental performance. Green Premium promises compliance with the latest regulations, transparency on environmental impacts, as well as circular and low-CO2 products.