How many batteries can be connected to Easy UPS SRV6KL-IN?
1. Connect twenty(20) SMF 12 V batteries in series.
2. The UPS is intended for use with 240 VDC nominal battery voltage. The external battery system connected to the UPS must not exceed 192 VDC nominal voltage.
2. The UPS is intended for use with 240 VDC nominal battery voltage. The external battery system connected to the UPS must not exceed 192 VDC nominal voltage.
Published for:APC India