How to set output voltage in UPS SRC1KXLI through display ?

Published date: 28 November 2019


Kindly find the steps to configure output voltage for UPS SRC1KXLI 
1.Press SELECT button to enter the UPS settings.
2. Navigate through the parameters using SELECT button.
3. Press ENTER/MUTE button to edit a Output voltage. The icon starts flashing to indicate it is ready for editing.                                                                                                                                                      
4. user selectable options are 200, 208, 220, 230 (default), 240 Vac.                                                                                                                                                                                                                                        
5.Press ENTER/MUTE button to select the desired option, the flashing of icon stops after the selection.                                                                                                                                                                 
Note:Output voltage can be set only when ups is in standby mode.    