Video:How to configure overload warning in ATS through NMC.

Published date: 31 July 2018

Step 1- Select Configuration=>ATS=>Load 
Step 2-Set values for Low Load Warning
The threshold for Low Load Warning. This value must be less than the Near Overload Warning. A value of zero effectively disables the warning.
Step 3-Set value for Near Overload Warning
The threshold for Near Overload Warning. This value must be greater than the Low Load Warning and less than or equal to the Overload Alarm.
Step 4-Set value for Overload Alarm
The threshold for Overload Alarm. This value must be greater than or equal to the Near Overload Warning.
Step 5-After configuration 'Apply'  changes.

 