Our Brands

APC Silcon 40kW 400V UPS w/ 2 Batt. Drawers w/ RAL 2003/ Build in DC breaker

SL40KHB0X392

notification_critical
information_stroke
  • What does the end of commercialization mean ?

    End of commercialization is the last date Schneider Electric will accept an offer for this reference. However, after Sales Services (repair, spare parts, etc.) will continue until its end of life.

  • Need more help

    Contact Customer Care Center - available 24 a day.

notification_critical
information_stroke
  • What does the end of standard service mean ?

    End of standard service is the last date Schneider Electric will be able to provide you maintenance services (repair, spare parts, etc.).

  • Need more help

    Contact Customer Care Center - available 24 a day.

SL40KHB0X392 has not been replaced. Please contact your customer care centre for more information.
arrow2_down

Compatible Software

arrow2_down

Specifications

Overview
Lead timeUsually Ships within 4 Weeks
General
provided equipmentInstallation guide
Parallel card
Triple chassis for 3 SmartSlots
User manual
Web/SNMP management card
performance multiplier0
Number of tare power850 W
Number of power module free slots0
Number of power module filled slots0
redundantNo
size UPS versionInternetworking
Server
Telecom
UPS sizeL
value multiplier0
Physical
colourOrange
depth80 cm
height140 cm
mounting locationFront
mounting preferenceNo preference
net weight358.64 kg
mounting modeNot rack-mountable
USB compatibleNo
width100 cm
Input
network frequency50 Hz programmable +/- 0.5 / 1 / 2 / 4 / 6 / 8 %
60 Hz programmable +/- 0.5 / 1 / 2 / 4 / 6 / 8 %
number of input connectors1 hard wire 4-wire (3P + N)
1 hard wire 4-wire (3P + PEN)
1 hard wire 5-wire (3P + N + E)
input voltage limits323...437 V adjustable 380 V
340...460 V adjustable 400 V
357...477 V adjustable 415 V
323...437 V 380 V
340...460 V 400 V
353...477 V 415 V
number of cables1
input voltage400 V 3 phases
cos phi0.99
Output
rated power in W40000 W
Maximum configurable power in W40000 W
harmonic distortionLess than 3 %
output frequency50 Hz sync to mains
60 Hz sync to mains
60 Hz +/- 0.1 % for 60 Hz nominal unsynchronised
50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised
crest factorUnlimited
UPS typeDelta conversion on-line
Wave typeSine wave
bypass typeBuilt-in static bypass
curve equationEfficiency
curve load maximum100 %
curve X-axis maximum100 %
curve X-axis minimum0 %
curve X-axis titleLoad
curve X-axis unitsPercentage
curve Y-axis maximum100 %
curve Y-axis minimum50 %
curve Y-axis titleEfficiency
curve Y-axis unitsPercentage
efficiency97 % (full load)
output voltage230 V
400 V 3 phases
Maximum configurable power in VA40000 VA
rated power in VA40000 VA
Conformance
product certificationsCE
TÜV
standardsEN 50091-1
EN 50091-2
ISO 9001
Environmental
ambient air temperature for operation0…40 °C
relative humidity0…95 %
operating altitude0...10000 ft
ambient air temperature for storage-50…40 °C
storage Relative Humidity0…95 %
storage altitude0.00…15240.00 m
acoustic level55 dBA
heat dissipation5118 Btu/h
IP degree of protectionIP30
IP31 optional
Batteries & Runtime
number of battery filled slots0
number of battery free slots0
additional informationConfigurable for 380 : 400 or 415 V 3 Phase nominal output voltage
liquid value0
battery curveB
Battery power in VAH0 VAh runtime
extended runtime0
Communications & Management
free slots2
preinstalled deviceNetwork management card
control panelMultifunction LCD status and control console
alarmBeep for each 52 alarm conditions
Emergency power offYes
Packing Units
Package 1 Weight380.92 kg
Package 1 Height160 cm
Package 1 width110 cm
Package 1 Length90 cm
Number of Units in Package 31
Contractual warranty
Warranty1 year repair or replace
arrow2_down

Documents

arrow2_down

Software and Firmware