Our Brands

MGE Galaxy 5500 30KVA 400V Integrated Parallel UPS 15 Minutes, Start-up 5x8

G55TUPSM30HB15S

notification_critical
information_stroke
  • What does the end of commercialization mean ?

    End of commercialization is the last date Schneider Electric will accept an offer for this reference. However, after Sales Services (repair, spare parts, etc.) will continue until its end of life.

  • Need more help

    Contact Customer Care Center - available 24 a day.

notification_critical
information_stroke
  • What does the end of standard service mean ?

    End of standard service is the last date Schneider Electric will be able to provide you maintenance services (repair, spare parts, etc.).

  • Need more help

    Contact Customer Care Center - available 24 a day.

arrow2_down
arrow2_down
arrow2_down

Specifications

Overview
PresentationA versatile 3-phase UPS for facility, industrial and data center applications. Configurable system with a comprehensive range of accessories to meet your application demands.
Lead timeUsually Ships within 2 Weeks
Main
Run time for load
W
information_circle
Enter the total load (power draw) of all devices that will be protected by the UPS. This will be used to estimate the run time of your devices during a total power outage. Adding run time increases availability by allowing the system to operate through longer outages without shutting down.
Min-max: 2700-27000 W
Max. Capacity Used
information_circle
The maximum percentage of UPS capacity used to support your specified load.
rated power in W27000 W
rated power in VA30000 VA
output connector typeHard wire 4-wire (3P + E) 1
Main Output Voltage400 V 3 phases
Other Output Voltage380 V
415 V
Other Input Voltage380 V
415 V
Main Input Voltage400 V 3 phases
General
provided equipmentInstallation guide
Network management card
Start-up service
User manual
bypass voltage tolerance+/- 10 % settable from +/- 4/6/8 and 10 %
max bypass input current43 A
Number of power module free slots0
Number of power module filled slots0
redundantNo
Physical
depth85.5 cm
height190 cm
mounting preferenceNo preference
net weight958 kg
USB compatibleNo
width71.2 cm
Input
network frequency45...65 Hz
number of input connectors1 hard wire 4-wire (3P + E)
1 hard wire 4-wire (3P + N)
input voltage limits250...470 V adjustable
323...437 V 380 V
340...460 V 400 V
353...477 V 415 V
maximum input current46 A
switching current capacity125 A
max short time withstand current20 kA
input harmonic distortionLess than 3 % for full load
input protection type3-pole circuit breaker
inrush current200 A peak
load power factor0.9
Input Power Factor at Full Load1
Output
Maximum configurable power in W27000 W
harmonic distortionLess than 2 %
output frequency50/60 Hz +/- 3 Hz user adjustable +/- 0.1 Hz sync to mains
50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised
crest factor3 : 1
Wave typeSine wave
output voltage tolerance+/- 1% static and +/- 5% at 100% load step
output harmonic distortion< 1% linear load and < 2.5% non-linear load
output overload operation10 minutes at 125% and 60 seconds at 150%
required output current protection43 A
bypass typeBuilt-in maintenance bypass
Built-in static bypass
Optional external bypass
efficiency92.4 % (full load)
maximum output current190 A
Maximum configurable power in VA30000 VA
Conformance
product certificationsCE
TÜV
VDE
standardsIEC 62040-1-2
EN/IEC 62040-2
EN/IEC 62040-3
ISO 9001
Environmental
ambient air temperature for operation0…40 °C
relative humidity0…95 %
operating altitude0...3333 ft
ambient air temperature for storage-20…45 °C
storage Relative Humidity0…95 %
storage altitude0.00…12192.00 m
acoustic level55.5 dBA
IP degree of protectionIP20
Batteries & Runtime
Run TimeView Runtime Graphaction_new_window
battery typeVRLA
number of battery filled slots0
number of battery free slots0
Battery recharge time10 h
additional informationConfigurable for 380 : 400 or 415 V 3 Phase nominal output voltage
battery voltage432 V
battery charger power1449 W rated
Battery power in VAH14500 VAh runtime
battery life8…10 year(s)
Battery graph commentsEstimated runtimes based on battery vendor data, at typical environmental conditions, with no electrical input and balanced PF = 0.9 output.
extended runtime0
Communications & Management
free slots2
preinstalled deviceNetwork management card 2 with environmental monitoring, out of band access and Modbus
control panelMultifunction LCD status and control console
Emergency power offYes
Packing Units
Package 1 Weight978 kg
Package 1 Height203 cm
Package 1 width98 cm
Package 1 Length96 cm
Contractual warranty
Warranty1 year on-site repair or replace with factory authorized Start-Up, 1 year (parts only)
arrow2_down

Sustainability

Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-class environmental performance. Green Premium promises compliance with the latest regulations, transparency on environmental impacts, as well as circular and low-CO2 products.

EU RoHS Directive

Under investigation

Under investigation

arrow2_down

Documents

arrow2_down

Software and Firmware