Specifications

Overview
PresentationHighly efficient, scalable, 3-phase power protection with flexible operating modes and ECOnversion™ for large facilities, data centers, and business critical applications.
Lead timeSpecial Order - Call for Quoted Lead Times
Main
Main Input Voltage400 V 3 phases
Other Input Voltage380 V
415 V
440 V
Main Output Voltage400 V 3 phases
Other Output Voltage380 V
415 V
440 V
rated power in W625 kW
rated power in VA625 kVA
battery typeExternal battery system
provided equipmentInstallation guide
Start-up service
General
redundantNo
Physical
colourWhite
height197 cm
width330 cm
depth90 cm
net weight2420 kg
USB compatibleNo
Input
network frequency40...70 Hz
maximum input current1063 A
max short time withstand current100 kA
input harmonic distortionLess than 3 % for full load
load power factorFrom 0.7 leading to 0.5 lagging without any derating
Output
Maximum configurable power in W1000 kW
output frequency50 Hz sync to mains
60 Hz sync to mains
50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised
crest factor3 with THC <5%
Wave typeSine wave
output harmonic distortion< 2% linear load and < 3% non-linear load
output overload operation10 minutes at 125% and 60 seconds at 150%
Maximum configurable power in VA1000 kVA
Conformance
product certificationscUL listed
C-Tick
CE
standardsIBC 2012
IEC 62040-1-1
IEC 62040-2
IEC 62040-3
IEC 62040-4
ISTA 2B
UL 1778 5th edition
Environmental
ambient air temperature for operation0…40 °C
relative humidity0…95 % non-condensing
operating altitude0...3333 ft
ambient air temperature for storage-15…40 °C
storage Relative Humidity0…95 % Non-condensing
storage altitude0.00…15240.00 m
acoustic level69.5 dBA
heat dissipation112040 Btu/h
IP degree of protectionIP20
Batteries & Runtime
EfficiencyView Efficiency Graphaction_new_window
number of battery filled slots0
number of battery free slots0
battery voltage480 V
discharge battery voltage384 V DC
Battery power in VAH0 VAh runtime
extended runtime0
Communications & Management
free slots2
preinstalled deviceNetwork management card 2 with environmental monitoring, out of band access and Modbus
control panel7" touch screen display
alarmAudible and visible alarms prioritized by severity
Packing Units
Package 1 Weight3288 kg
Package 1 Height215 cm
Package 1 width391 cm
Package 1 Length106 cm
Contractual warranty
Warranty1 year on-site repair or replace with factory authorized Start-Up