{"support":{"yesButton":"Oui","noButton":"Non","feedback":{"title":"Quelles améliorations pouvons-nous apporter ?"},"submitButton":"Soumettre","successMessage":"Merci de nous avoir fait part de vos commentaires.","title":"Cela vous a-t-il été utile ?","feedbackPercentLabel":"personnes ont trouvé cela utile","captcha":{"error":"Veuillez cocher la case appropriée."}}}
Consulter notre FAQ
{"searchBar":{"inputPlaceholder":"Rechercher par mot-clé ou poser une question","searchBtn":"Rechercher","error":"Veuillez saisir un mot-clé pour effectuer une recherche"}}
This document describes how the Magnum VS DC Power shelf operates when the controller card is removed.
Issue:
This document describes how the Magnum VS DC Power shelf operates when the controller card is removed.
Product Line:
DC
Environment:
All Magnum VS models, All Serial Numbers
Cause:
Product Information
Resolution:
The Controller card on the Magnum VS stores the user settings, should this card become faulty it can be ‘hot-swapped’.
When the Controller Card is removed the Rectifiers in the unit default the Output Voltage to 54.5v and continue to load share until a Controller card is replaced into the unit and new settings are entered.