Proper use of a "Make Before Break" bypass panel with an SURT or SRT UPS

When moving from Normal to Test mode:

Place UPS into internal Bypass
Confirm UPS is in Bypass
It is now safe to move the SBP to Test mode
 
When moving from Test to Bypass or vice versa:
UPS can be in any state
 
When moving from Test back to Normal:

Place UPS into internal Bypass
Confirm that UPS is in Bypass
Move SBP to Normal
Confirm UPS has no faults and input is acceptable to bring online.
Take UPS out of internal Bypass
 