Video: Clearing unit run hour violations on an Chilled Water Uniflair

Issue:
Tis document describes how to clear Unit Run Hours Violation on Uniflair Chilled Water cooling systems.
 
Product line:
Uniflair: TDCV700X, TDCV1000X, TDCV1200X, TDCV1700X, TDCV2500X, TDCV3400X, TDCV4000X, TDCV4300X, TUCV700X, TUCV1000X, TUCV1200X, TUCV1700X, TUCV2500X, TUCV3400X, TUCV4000X, TUCV4300X, HDCV4500X, HDCV5000X
 
Environment:
All Serial Numbers.
 
Cause:
Install, Repair.
 
Resolution
 
Press PRG
 
Use the DOWN arrow to scroll to Hourmeter Settings.
 
Press ENTER.
 
Use the DOWN arrow to scroll to Unit Run Hours.
 
Press ENTER twice..
 
Press the DOWN arrow once.
 
Press ENTER again to clear run hours.
 
Press ESC three times to exit back to main menu.