{"searchBar":{"inputPlaceholder":"Busca por palabra clave o haz una pregunta","searchBtn":"Buscar","error":"Ingresa una palabra para buscar"}}
{}

Nuestras marcas

{"support":{"yesButton":"Sí","noButton":"No","feedback":{"title":"¿Qué podemos hacer para mejorar?"},"submitButton":"Enviar","successMessage":"Gracias por tus comentarios","title":"¿Te fue de ayuda?","feedbackPercentLabel":"de las personas encontraron esto útil","captcha":{"error":"Por favor, marca una casilla"}}}
Buscar Preguntas Frecuentes

Power Consumption of APC Rack Power Distribution Unit (PDU) / Automatic Transfer Switch (ATS) Products

 
 

 
Rack Power Distribution Unit (PDU) Type
 

Total Power Consumption (no outlets "ON")

 Wattage Draw Per "ON" Outlet

 Total Power Consumption (all outlets "ON" - assuming up to 24 outlets)


Metered (AP71XX, AP78XX)
 

N/A

N/A

approx. 5 watts



Metering By Outlet (MBO) (AP84XX)

 
N/AN/Aapprox. 11.5 watts


Metered (AP88XX)
 

N/A

N/A

5 watts


Switched (AP79XX)
 

approx. 5 watts

approx. 1 watt

approx. 29 watts


Switched (AP89XX)
 

5 watts

.5 watts

17 watts


Switched with Metering By Outlet (MBO) (AP86XX)
 

18 watts

.25 watts

24 watts


Rack Automatic Transfer Switch (ATS) Type
 

Total Power Consumption (no outlets "ON") Wattage Draw Per "ON" Outlet Total Power Consumption (all outlets "ON")


All models (AP77XX)
 

N/A

N/A

approx. 20 watts

All models (AP44XXN/AN/A< 20 watts

 

Note: These measurements don't include resistive losses due to current flow through the Rack PDU or Rack ATS meaning, they are only the fixed losses of the PDU or ATS associated with communications, measurements, and relay control.


 

¿No encuentras lo que estás buscando?

Comunícate con nuestro equipo de Atención al Cliente para recibir soporte técnico, asistencia para quejas y más.