{"support":{"yesButton":"Ja","noButton":"Nein","feedback":{"title":"Was können wir tun, um zu verbessern?"},"submitButton":"Senden","successMessage":"Vielen Dank für Ihre Rückmeldung.","title":"War das hilfreich?","feedbackPercentLabel":"aller Betrachter fanden die Antwort hilfreich","captcha":{"error":"Aktivieren Sie das Kontrollkästchen"}}}
FAQs durchsuchen
{"searchBar":{"inputPlaceholder":"Nach Stichwort suchen oder Frage stellen","searchBtn":"Suchen","error":"Bitte geben Sie ein Stichwort für die Suche ein."}}
Configuring Post-only Mode for Netbotz Version 2 and 3 Appliances
Issue:
Configuring Post-only Mode for Netbotz Appliances
Product Line:
NetBotz.
Environment:
NetBotz version 2 and 3
StruxureWare Data Center Expert
Cause:
NetBotz posting configuration. This may be necessary if the NetBotz appliances can not be polled by StruxureWare but the NetBotz appliance can post.
Resolution:
NOTE: Legacy software NetBotz Central can not communicate with version 3 appliances.
Configuring Post-only Mode for Netbotz Appliances
Product Line:
NetBotz.
Environment:
NetBotz version 2 and 3
StruxureWare Data Center Expert
Cause:
NetBotz posting configuration. This may be necessary if the NetBotz appliances can not be polled by StruxureWare but the NetBotz appliance can post.
Resolution:
Appliances can only be placed in Post-only mode from the Advanced View. To place an appliance in Post-only Mode perform the following steps:
- Select “Tools” then “Advanced” then “Post Only Mode”.
- Enter the hostname or IP address of the NetBotz Central the appliance will be "posting" to as well as the appropriate authentication data. Enter a username and password that has administrator level privilege on the NetBotz Central or StruxureWare Data Center Expert server..
- When all of the information is correctly entered, click on the OK button. Once the OK button is pressed, the following screen will appear with status information.
- Click on the "Post to Data Center Expert now" button to check the connection and ensure the information is correctly entered.
NOTE: Legacy software NetBotz Central can not communicate with version 3 appliances.