FAQs durchsuchen
{"searchBar":{"inputPlaceholder":"Nach Stichwort suchen oder Frage stellen","searchBtn":"Suchen","error":"Bitte geben Sie ein Stichwort für die Suche ein."}}
What are the pinouts for the Output Relay on the Environmental Monitoring Unit (AP9319) and the Environmental Management System (AP9320)?
Below are the pinouts:
Pin # | Description |
1 | No Connection |
2, 3 | Normally Closed (NC) Contact |
4, 5 | Common |
6, 7 | Normally Open (NO) Contact (recommended connection) |
8 | No Connection |
Relay ratings: 1A, 30V AC/DC
Since the user interface allows for either 'normally open' or 'normally closed,' APC recommends using only the normally open contacts and configuring the 'normal' state in the user interface.
Published for:APC Switzerland
War das hilfreich?
Weitere Produktinformationen
Kategorie:
Weitere Produktinformationen
Kategorie: