Our Brands

APC Silcon 10kW 208V UPS

SL10KF

notification_critical
information_stroke
  • What does the end of commercialization mean ?

    End of commercialization is the last date APC will accept an offer for this reference. Howerver, After Sales Services (repair, spare parts, etc.) will continue until its end of life.

  • Need more help

    Contact Customer Care Center - available 24 a day.

notification_critical
information_stroke
  • What does the end of standard service mean ?

    End of standard service is the last date APC will be able to provide you maintenance services (repair, spare parts, etc.).

  • Need more help

    Contact Customer Care Center - available 24 a day.

SL10KF has not been replaced. Please contact your customer care center for more information.
arrow2_down

Compatible Software

arrow2_down

Specifications

Overview
Lead timeWhile Supplies Last
Main
Main Input Voltage208 V 3 phases
Main Output Voltage120 V
208 V
208 V 3 phases
Rated power in W10000 W
Rated power in VA10000 VA
output connector typeHard wire 5-wire (3P + N + E) 1
connections - terminals1 screw terminals
Number of rack unit0U
number of cables1
Battery typeExternal battery system
provided equipmentInstallation guide
Parallel card
Triple chassis for 3 SmartSlots
User manual
Web/SNMP management card
General
Number of power module free slots0
Number of power module filled slots0
RedundantNo
Physical
colourDark green NCS 7020-B50G)
Light grey NCS 2703-G84Y)
Height55.12 in (140 cm)
Width23.62 in (60 cm)
Depth31.50 in (80 cm)
Net weight420.88 lb(US) (190.91 kg)
Mounting locationFront
Mounting preferenceNo preference
Mounting modeNot rack-mountable
USB compatibleNo
Input
network frequency50 Hz programmable +/- 0.5 / 1 / 2 / 4 / 6 / 8 %
60 Hz programmable +/- 0.5 / 1 / 2 / 4 / 6 / 8 %
number of input connectors1 hard wire 5-wire (3P + N + E)
input voltage limits170...230 V 208 V
177...239 V 208 V
187...242 V 220 V
Input Power Factor at Full Load0.99
Output
Maximum configurable power in W10000 W
Harmonic distortionLess than 3 %
output frequency50 Hz programmable +/- 0.5 / 1 / 2 / 4 / 6 / 8 % sync to mains
60 Hz programmable +/- 0.5 / 1 / 2 / 4 / 6 / 8 % sync to mains
60 Hz +/- 0.1 % for 60 Hz nominal unsynchronised
50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised
Crest factorUnlimited
UPS typeDelta conversion on-line
Wave typeSine wave
Bypass typeBuilt-in static bypass
efficiency93.6 % full load)
Maximum output current28 A
Maximum configurable power in VA10000 VA
Conformance
product certificationscUL listed
UL listed
StandardsFCC part 15 class A
ISO 14001
ISO 9001
UL 1778
Environmental
Ambient air temperature for operation32…104 °F (0…40 °C)
relative humidity0…95 %
Operating altitude0...3333 ft
Ambient air temperature for storage-58…104 °F (-50…40 °C)
storage Relative Humidity0…95 %
Storage altitude0…50000 ft (0.00…15240.00 m)
Acoustic level55 dBA
Heat dissipation2388 Btu/h
NEMA degree of protectionNEMA 1
NEMA 12 optional)
Batteries & Runtime
Number of battery filled slots0
Number of battery free slots0
Additional informationA Battery Breaker Box is required for all 10kW External Battery Solutions.
Configurable for 200 : 208 or 220V 3 Phase nominal output voltage
Battery power in VAH0 VAh runtime
Extended runtime1
Communications & Management
Free slots2
Preinstalled deviceNetwork management card
control panelMultifunction LCD status and control console
AlarmBeep for each 52 alarm conditions
Emergency power offYes
Contractual warranty
Warranty1 year (parts only), optional on-site warranties available, optional extended warranties available