MGE Galaxy 5500 40kVA 400-415V Integrated Parallel UPS Off Shore IP22 RAL 7035, Start-up 5X8
G55TUPM40HXS
Discontinued on:06 September 2021
To be end-of-service on:31 December 2030
Recommended replacement(s)
Specifications
Presentation | UPS is designed to meet the offshore standard requirement. |
---|---|
Lead time | Special Order - Call for Quoted Lead Times |
Main Input Voltage | 400 V 3 phases |
---|---|
Other Input Voltage | 380 V 415 V |
Main Output Voltage | 400 V 3 phases |
Other Output Voltage | 380 V 415 V |
Rated power in W | 36000 W |
Rated power in VA | 40000 VA |
Battery type | External battery system |
Provided equipment | Installation guide User manual |
Bypass wiring configuration | 4 wire (3P + N) 5 wire (3P + N + E) |
---|---|
Bypass voltage tolerance | +/- 10 % settable from +/- 4/6/8 and 10 % |
Max bypass input current | 58 A |
Bypass current protection | 100 A |
Number of power module free slots | 0 |
Number of power module filled slots | 0 |
Redundant | No |
Colour | Light grey |
---|---|
Height | 85.83 in (218 cm) |
Width | 28.03 in (71.2 cm) |
Depth | 33.66 in (85.5 cm) |
Net weight | 1005.31 lb(US) (456 kg) |
Mounting preference | No preference |
USB compatible | No |
Network frequency | 45...65 Hz |
---|---|
Number of input connectors | 1 hard wire 4-wire (3P + E) 1 hard wire 4-wire (3P + N) |
Input voltage limits | 323...437 V 380 V 340...460 V 400 V 353...477 V 415 V |
Maximum input current | 77 A |
Switching current capacity | 125 A |
Max short time withstand current | 20 kA |
Input harmonic distortion | Less than 5 % for full load |
Input protection type | GL fuse |
Load power factor | 0.9 |
Input Power Factor at Full Load | 1 |
Maximum configurable power in W | 36000 W |
---|---|
Harmonic distortion | Less than 2 % |
Output frequency | 50 Hz programmable +/- 0.5 / 1 / 2 / 4 / 6 / 8 % sync to mains 50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised |
Crest factor | 3 : 1 |
Wave type | Sine wave |
Output voltage tolerance | +/- 2% static and 100% load step |
Output harmonic distortion | < 1% linear load and < 2.5% non-linear load |
Output overload operation | 10 minutes at 125% and 60 seconds at 150% |
Required output current protection | 58 A |
Neutral output current | 87 A |
Bypass type | Built-in maintenance bypass Built-in static bypass Optional external bypass |
Efficiency | 91 % full load) 85 % half load) |
Maximum output current | 190 A |
Maximum configurable power in VA | 40000 VA |
Product certifications | CE TÜV VDE |
---|---|
Standards | EN/IEC 62040-1 EN/IEC 62040-2 EN/IEC 62040-3 IEC 62040-2 ISO 9001 |
Ambient air temperature for operation | 32…104 °F (0…40 °C) |
---|---|
Relative humidity | 0…95 % |
Operating altitude | 0...3333 ft |
Ambient air temperature for storage | -4…113 °F (-20…45 °C) |
Storage Relative Humidity | 0…95 % |
Storage altitude | 0…12000 ft (0.00…3657.60 m) |
Acoustic level | 65 dBA |
IP degree of protection | IP20 IP32 |
Number of battery filled slots | 0 |
---|---|
Number of battery free slots | 0 |
Additional information | Configurable for 400 or 415 V 3 Phase nominal output voltage |
Battery charger power | 9300 W rated |
Battery power in VAH | 93 VAh runtime |
Battery life | 8…10 year(s) |
Battery option | G55TE-BB40K30 1 40090 VAh |
Extended runtime | 0 |
Free slots | 3 |
---|---|
Preinstalled device | Network management card 2 with environmental monitoring, out of band access and Modbus - Schneider |
Control panel | Multifunction LCD status and control console |
Emergency power off | Yes |
Unit Type of Package 1 | Db |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 90.55 in (230 cm) |
Package 1 Width | 47.24 in (120 cm) |
Package 1 Length | 42.52 in (108 cm) |
Package 1 Weight | 1058.22 lb(US) (480 kg) |
Number of Units in Package 2 | 1 |
Number of Units in Package 3 | 1 |
Warranty | 1 year (parts only), 1 year on-site repair or replace with factory authorized Start-Up |
---|
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-class environmental performance.
Green Premium promises compliance with the latest regulations, transparency on environmental impacts, as well as circular and low-CO2 products.
Learn moreEU RoHS Directive
Under investigation
Documents
Software and Firmware
Need more information? Check our technical FAQs!
Easily find answers to the most frequently asked questions.
G55TUPM40HXS is replaced by the following product range: