Our Brands

APC Easy UPS, 1200VA, Tower, 230V, 6x IEC C13 Outlets, AVR

BVX1200LI

BVX1200LI has not been replaced. Please contact your customer care center for more information.
notification_ok
Online stores
arrow2_down

Specifications

Overview
Lead timeUsually in Stock
Main
Run time for load
W
information_circle
Enter the total load (power draw) of all devices that will be protected by the UPS. This will be used to estimate the run time of your devices during a total power outage. Adding run time increases availability by allowing the system to operate through longer outages without shutting down.
Min-max: 65-650 W
Max. Capacity Used
information_circle
The maximum percentage of UPS capacity used to support your specified load.
Main Input Voltage230 V AC 1 phase
Main Output Voltage230 V AC 1 phase
Rated power in W650 W
Rated power in VA1200 VA
Input Connection TypeIEC 60320 C14
output connection type6 IEC 320 C13
Cable length4 ft (1.22 m)
Number of cables1
Battery typeLead-acid battery
Provided equipmentUser manual
General
Max runtime120 min
Number of power module free slots0
Number of power module filled slots0
RedundantNo
UPS sizeWS
Physical
ColourBlack
Height7.48 in (19 cm)
Width5.51 in (14 cm)
Depth15.35 in (39 cm)
Net weight16.53 lb(US) (7.5 kg)
Mounting supportFloor
Mounting preferenceNo preference
Mounting modeNot rack-mountable
Two post mountable0
USB compatibleNo
Input
Network frequency50/60 Hz +/- 5 Hz auto-sensing
Input voltage limits140...300 V 230 V AC
Cos phi0.51
Output
Maximum configurable power in W650 W
Output frequency50/60 Hz +/- 1 Hz sync to mains
UPS typeLine interactive
Wave typeStepped approximation to a sinewave
Full load runtime00:01:00 650 W
Graph display1
Half load runtime00:05:00 300 W
Maximum configurable power in VA1200 VA
Transfer time6 ms typical : 10 ms maximum
Conformance
Product certificationsCE
CB
StandardsEN/IEC 62040-1:2019/A11:2021
EN/IEC 62040-2:2006/AC:2006
EN/IEC 62040-2:2018
Equipment protection policyLifetime : 50000 euros
Environmental
Ambient air temperature for operation32…104 °F (0…40 °C)
Relative humidity0…95 % non-condensing
Operating altitude0...3000 m
Ambient air temperature for storage5…104 °F (-15…40 °C)
Storage Relative Humidity0…95 % non-condensing
Storage altitude0.00…9842.52 ft (0…3000 m)
Acoustic level40 dBA
IP degree of protectionIP20
Batteries & Runtime
Run TimeView Runtime Graphaction_new_window
EfficiencyView Efficiency Graphaction_new_window
Number of battery filled slots0
Number of battery free slots0
Battery recharge time8 h
Battery voltage12 V
Battery capacity9.0 Ah
Battery life2…3 year(s)
Replacement batteryAPCRBC175action_new_window
Extended runtime0
Communications & Management
AlarmAlarm when on battery : distinctive low battery alarm : overload continuous tone alarm
Surge Protection and Filtering
Surge energy rate273 J
Packing Units
Unit Type of Package 1Db
Number of Units in Package 11
Package 1 Height11.69 in (29.7 cm)
Package 1 Width19.49 in (49.5 cm)
Package 1 Length9.25 in (23.5 cm)
Package 1 Weight18.74 lb(US) (8.5 kg)
SCC1410731304404504
Contractual warranty
Warranty2 years repair or replace
arrow2_down

Sustainability

Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-class environmental performance. Green Premium promises compliance with the latest regulations, transparency on environmental impacts, as well as circular and low-CO2 products.
Learn morearrow2_left
Well-being performance

REACh free of SVHC

notification_ok

Mercury free

notification_ok

RoHS exemption information

REACh Regulation

EU RoHS Directive

China RoHS Regulation

China RoHS declaration

Pro-active China RoHS declaration (out of China RoHS legal scope)

arrow2_down

Documents

arrow2_down

Software and Firmware

Need more information? Check our technical FAQs!