Hello,
Log Out
Log In
New Customer?
Register Now
Power
Uninterruptible Power Supply (UPS)
Surge Protection and Power Conditioning
Cooling
Modular Access Floor
Containment and Air Distribution
Chillers
Close Coupled Air Conditioners
Room Air Conditioners
Security and Environmental Monitoring
Sensors / Cameras / Licenses / Accessories
Security and Environmental Appliances
Racks and Accessories
LCD Monitors and KVM Switches
Rack and Enclosure Accessories
Racks and Enclosures
Data Center Containment
Power Distribution
Row 3 Phase Power Distribution
Rack Power Distribution
Transfer Switches
Prefabricated Data Center Modules
Power Modules
IT Modules
DATA CENTER SOFTWARE
Monitoring & Control
Software Services
Modelling and Planning
Operations
Services
Plan
Install
Operate
Optimize
Renew
Product Based Services
View All Solutions
Business Solutions
Home Solutions
Get Support
Need Help? Start here
Product Documents & Software
Product Guides
Additional Links
Contact Us
Browse FAQs
Issue: This document will describe what are the operational conditions for an InRoom (Stulz) Unit.
Product line: ACPDX21-86, ACPCW40-150
Environment : All Serial Numbers
Cause: Install
Resolution:
The InRoom precision air conditioning units operate within the following ranges:
Room Conditions:
Between 18°C (64°F), 40% Relative Humidity (R.H.), and 27°C (81°F), 55% R.H.
Outdoor ambient conditions: Lower limit: -10°C (14°F) Upper limit: Depending on selected condenser
Voltage:
460V / 3ph / 60 Hz
208-230V / 3ph / 60 Hz
Voltage tolerance: +/- 10%
Voltage imbalance: <3%
Frequency:60 Hz +/- 1%
Chilled water-/cooling water pipes:
Maximum water head pressure: 10 bar (145 psi)
Maximum equivalent length of piping between the cooling unit and the air cooled condenser: 60 m (200 ft)
Maximum level difference between the condenser and the cooling unit: 5 m (16 ft) when the condenser is below the cooling unit
Storage conditions:
Temperature: -20 - +42°C (-4 - +107.6°F)
Humidity: (% R. H.): 5 - 95
Atmospheric pressure: 70 - 110 kPa (10 - 16 psi)
Design Conditions
Return air conditions for evaporator capacity (DX): 24°C (75°F) 50% R. H.
Return air conditions for cooling capacity (CW): 24°C (75°F) 50% R.H.
Entering water temperature (EWT) for CW coil: 7°C (44.6°F)
Leaving water temperature (LWT) for CW coil: 12°C (53.6°F)
Condensing temperature: 45°C (113°F)
Maximum condensing temperature: 60°C (140°F)
Cooling fluid (DX): 30% Glycol
Fluid inlet temperature (G): 30°C (86°F)
Fluid outlet temperature (G): 40°C (104°F)
Chilled water medium (CW): 0% Glycol
Data is valid for: 460V / 3ph /60 Hz
Downflow units with an external static pressure: 20 Pa (0.08 in w g)
Upflow units with an external static pressure: 50 Pa (0.20 in w g)