{"support":{"yesButton":"Ja","noButton":"Nein","feedback":{"title":"Was können wir tun, um zu verbessern?"},"submitButton":"Senden","successMessage":"Vielen Dank für Ihre Rückmeldung.","title":"War das hilfreich?","feedbackPercentLabel":"aller Betrachter fanden die Antwort hilfreich","captcha":{"error":"Aktivieren Sie das Kontrollkästchen"}}}
FAQs durchsuchen

Why has PowerChute Business Edition version 9.x, 10.x lost communication with UPS after communication cable has been unattached and reattached?

 

Issue:
After detaching communication cable and then reattaching communication cable PowerChute Business Edition does not reestablish communications with the UPS.

 

Product:
PowerChute Business Edition v9.x, 10.x 

 

Environment:
All supported OS communicating with UPS via USB or Serial

 

Cause:
Communications cable was unattached while PowerChute service or daemon was running on the OS.

 

Solution:

 1 – Stop PowerChute service or daemon before detaching and reattaching communications cable.

2 – If cable is unattached while the server or daemon is running you can re-establish communications by

            a: Stopping and restarting the server or daemon.

            b: If step a does not resolve the issue stop the service or daemon again, reattach the cable and then brain dead the UPS.  See Video: How to perform a cold start and brain dead on Smart-UPS for instructions on how to brain dead a Smart-UPS.

c: For other lost communication troubleshooting steps see Schneider Electric Video: Troubleshooting no communication between UPS and PowerChute Business Edition

 

 