MGE Galaxy 7000 300 kVA
G7TUPS300
Discontinued on:06 January 2022
To be end-of-service on:31 December 2031
Specifications
Presentation | A high-adaptability, 3-phase UPS that meets the unique requirements of medium to large data centers, industry, buildings, and mission-critical environments. This UPS includes ECO Mode, with cost-saving energy efficiency, and SPoT operation mode, which increases on-site test capability without additional load bank. |
---|---|
Lead time | Special Order - Call for Quoted Lead Times |
Main Input Voltage | 400 V 3 phases |
---|---|
Other Input Voltage | 380 V 415 V 450 V |
Main Output Voltage | 400 V 3 phases |
Other Output Voltage | 380 V 415 V 440 V |
Rated power in W | 270000 W |
Rated power in VA | 300000 VA |
output connector type | Hard wire 4-wire (3P + E) 1 Hard wire 5-wire (3P + N + E) 1 Hard wire 3-wire (3P) 1 Hard wire 4-wire (3P + N) 1 Hard wire 4-wire (3P + PEN) 1 |
Battery type | VRLA |
provided equipment | Installation guide Network management card User manual |
Bypass wiring configuration | 4 wire (3P + N) 5 wire (3P + N + E) |
---|---|
Bypass voltage tolerance | +/- 10 % settable from +/- 4/6/8 and 10 % |
Max bypass input current | 506 A |
Bypass current protection | 630 A |
Number of power module free slots | 0 |
Number of power module filled slots | 0 |
Redundant | No |
colour | Grey |
---|---|
Height | 190 cm |
Width | 141.2 cm |
Depth | 85.5 cm |
Net weight | 960 kg |
Mounting preference | No preference |
USB compatible | No |
network frequency | 45...65 Hz |
---|---|
number of input connectors | 1 hard wire 5-wire (3P + N + E) |
input voltage limits | 340...460 V 400 V |
Maximum input current | 442 A |
Switching current capacity | 630 A |
Max short time withstand current | 200 kA |
Input harmonic distortion | Less than 3 % for full load |
Input protection type | 3-pole circuit breaker |
Inrush current | 200 A peak |
Load power factor | 0.9 |
Input Power Factor at Full Load | 1 |
Maximum configurable power in W | 270000 W |
---|---|
Harmonic distortion | Less than 2 % |
output frequency | 50 Hz sync to mains 60 Hz sync to mains 50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised 60 Hz +/- 0.1 % for 60 Hz nominal unsynchronised |
Crest factor | 2.5 : 1 |
Wave type | Sine wave |
Output harmonic distortion | < 2% linear load and < 3% non-linear load |
Required output current protection | 433 A |
Neutral output current | 563 A |
Bypass type | Built-in maintenance bypass |
Maximum output current | 1281 A |
Maximum configurable power in VA | 300000 VA |
Product certifications | CE LCIE |
---|---|
standards | EN 60950 EN/IEC 62040-2 EN/IEC 62040-3 ISO 14001 ISO 9001 VFI-SS-111 |
Ambient air temperature for operation | 0…35 °C |
---|---|
relative humidity | 20…80 % |
Operating altitude | 0...3333 ft |
Ambient air temperature for storage | -25…40 °C |
storage Relative Humidity | 20…80 % |
Storage altitude | 0.00…9144.00 m |
Acoustic level | 70 dBA |
IP degree of protection | IP20 |
Efficiency | View Efficiency Graph |
---|---|
Number of battery filled slots | 0 |
Number of battery free slots | 0 |
Additional information | Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage |
Battery power in VAH | 0 VAh runtime |
Extended runtime | 0 |
Free slots | 1 |
---|---|
Preinstalled device | Network management card 2 with environmental monitoring, out of band access and Modbus - Schneider |
Control panel | Multifunction LCD status and control console |
Alarm | Audible and visible alarms prioritized by severity |
Emergency power off | Yes |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 203 cm |
Package 1 Width | 96 cm |
Package 1 Length | 152 cm |
Package 1 Weight | 980 kg |
Pallet unit layers | 1 |
Pallet layers | 1 |
Warranty | 1 year repair or replace |
---|
Documents
Software and Firmware
Need more information? Check our technical FAQs!
Easily find answers to the most frequently asked questions.